– 77 –
NOTE:
The tamper switch need not be
used for UL Household Fire or
Burglary installations. The
tamper switch must be
connected to an EOLR
supervised zone programmed
for trouble by day/alarm by
night (type 05) response as
shown for UL Commercial
Burglary installations.
When the keyswitch is
removed from the wall, the
tamper switch will open causing
a fault (trouble or alarm) on
zone 6 and causing the panel
to disable keyswitch operation
until the partition is disarmed
from a console.
RED
820ohms
YELLOW
RED
(ARMED)
BLACK
820ohms
WHITE
GREEN
(READY)
TAMPER SWITCH
(CONTACTS CLOSE WHEN
SWITCH DEPRESSED. SEE NOTE)
BROWN BROWN
BLUE BLUE
LOCK SWITCH
(NORMALLY OPEN)
2K EOLR
2K EOLR
TO AUX POWER
(TERMINAL 6)
TO J7/OUT 2
TO ZONE 7(+)
(TERMINAL 20)
TO ZONE 6(–)/ZONE 7(– )
(TERMINAL 19)
TO ZONE 6(+)
(TERMINAL 18)
TO J7/OUT 4
BROKEN LINES REPRESENT
INSTALLER WIRING CONNECTIONS
Figure 23. Remote Keyswitch Wiring
3. Connect the keyswitch Armed and Ready LEDs to the trigger connector as
shown in
Figure 23
.
Programming The Remote Keyswitch
1. With at least one two-line alpha keypad (5137AD/6139) wired and set to a
proper address, power up the system temporarily by plugging the AC
transformer into a 120VAC outlet (previously wired to the control).
2. Enter data field programming mode: [Installer Code] + 8 0 0.
Program the following data fields:
*15 KEYSWITCH ASSIGNMENT for the partition in which the keyswitch is
used.
*40 OPEN/CLOSE REPORTING FOR KEYSWITCH as desired. The
keyswitch reports as user "0."
The system automatically assigns Zone Type 10 to Zone 7 if a keyswitch is
enabled.
3. Press *99 to exit program mode..
If you need more information about actual programming procedures, see Section
4:
THE MECHANICS OF PROGRAMMING.
LED indications are defined as follows:
Green Red Meaning
Off Off Disarmed & Not Ready
On Off Disarmed & Ready
Off On Steady Armed Away
Off Slow Flash Armed Stay
Off Rapid Flash Alarm Memory