ADEMCO VISTA-50PEN Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Systèmes de contrôle d'accès de sécurité ADEMCO VISTA-50PEN. ADEMCO VISTA-50PEN User`s manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 214
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs

Résumé du contenu

Page 1 - &RPPHUFLDO%XUJODU\

K3271-1BX 9/0099,,6677$$33((11&RPPHUFLDO%XUJODU\3DUWLWLRQHG6HFXULW\6\VWHPZLWK6FKHGXOLQJ,QVWDOODWLRQDQG6HWXS*XLGH*ARMEDREADYPANICOFF

Page 2

VISTA-50PEN Installation and Setup Guidex

Page 3 - Table of Contents

VISTA-50PEN Installation and Setup Guide17-2Wiring the 4100APGThe 4100APG may be used either with or without a serial printer. The 4100APG connects to

Page 4

Section 17 – 4100APG Pager Interface17-3With the Event Log PrinterThe serial printer must be configured for 1200 baud rate, seven data bits, even pari

Page 5

VISTA-50PEN Installation and Setup Guide17-4Programming the Control for the Pager• In field *64 enter 1 to enable the 4100APG pager interface.• In fie

Page 6

18-1 SECTION 18 Final Power-Up Procedure•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Earth Ground Considerat

Page 7

VISTA-50PEN Installation and Setup Guide18-2Earth Ground ConsiderationsIn order for the lightning transient protective devices in this product to be e

Page 8 - List of Figures

Section 18 – Final Power-Up Procedure18-3NO CONNECTIONTRANSFORMER16.5VAC, 40VAADEMCO No.1361or 4300, XM10E, orXF10 if X-10 DEVICESWILL BE USED.Connect

Page 9

VISTA-50PEN Installation and Setup Guide18-4Determining the Control Panel Power Supply LoadUse the following tables to calculate the total current for

Page 10

Section 18 – Final Power-Up Procedure18-52. In table 2, enter devices used on Auxiliary Power. Calculate standby and alarm currents,then add to get Au

Page 11 - General Description

VISTA-50PEN Installation and Setup Guide18-64. In table 4, enter the total calculated subtotals of all listed outputs from Tables 1 through3, then add

Page 12 - Zone Expansion

Section 18 – Final Power-Up Procedure18-7Battery Capacity Calculation TableUsing the total calculated from Table 4, calculate the battery capacity req

Page 13

1-1 SECTION 1 General Description••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General♦ Features•••••••••••••••••••••••••••••••••

Page 14

VISTA-50PEN Installation and Setup Guide18-8

Page 15

19-1 SECTION 19 The Mechanics of Programming•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Using Data Field Program Mode♦ Entering

Page 16

VISTA-50PEN Installation and Setup Guide19-2Moving from One Page of Programming to AnotherThe data fields are grouped into four levels (referred to as

Page 17

Section 19 - The Mechanics of Programming19-3To program system-wide data fields, do the following:Step Action1 Enter Program Mode: [Installer Code] +

Page 18 - Common Lobby Logic

VISTA-50PEN Installation and Setup Guide19-4PROGRAMMING PARTITION-SPECIFIC FIELDSPress *91 to select a partition.↓Enter the partition to be programmed

Page 19 - COMMON LOBBY

20-1 SECTION 20 Zone Type Definitions•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Zone Number Designations♦ Zone Type Definitions

Page 20 - Codes with Non-Global Arming

VISTA-50PEN Installation and Setup Guide20-2Type 02: Entry/Exit #2 BurglaryProvides a secondary entry delay whenever the zone is faulted and the syste

Page 21

Section 20 – Zone Type Definitions20-3Type 10: Interior with DelayProvides entry and exit delays (using the programmed entry/exit time), if tripped wh

Page 22

VISTA-50PEN Installation and Setup Guide20-4

Page 23

21-1 SECTION 21 Zone Index/Zone Type Defaults•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Zone Index♦ Zone Type Defaults•••••••••

Page 24 - Cross Zoning

VISTA-50PEN Installation and Setup Guide1-2Wireless ExpansionSupports up to 128 wireless zones using 5881 type RF receiver (fewer if using hardwireand

Page 25 - Call Waiting Defeat Logic

VISTA-50PEN Installation and Setup Guide21-2Zone Type DefaultsFollowing are the zone type defaults for zones on the VISTA-50PEN:Zone # Zone Type Zone

Page 26

22-1 SECTION 22 Data Field Descriptions•••••••••••••••••••••••••••••••••••••••••••••••••The following is a description of all data fields provided by

Page 27 - Installing The Control

VISTA-50PEN Installation and Setup Guide22-2*14 ZONE 9 RESPONSE TIME[0]Enter 1 to set fast response mode (10 msec) for appropriate devices wired to zo

Page 28

Section 22 – Data Field Descriptions22-3*23 MULTIPLE ALARMS (partition-specific)[1]Determines whether or not more than one alarm can be sounded in a

Page 29

VISTA-50PEN Installation and Setup Guide22-4*30 TOUCHTONE OR ROTARY DIAL[0]Enter 1 if TouchTone service is being used.Enter 0 if rotary phone service

Page 30 - AC Transformer and Battery

Section 22 – Data Field Descriptions22-5*37 DOWNLOAD COMMAND ENABLESDialerShutdownSystemShutdownNotUsedRemoteBypassRemoteDisarmRemoteArmUploadProgramD

Page 31

VISTA-50PEN Installation and Setup Guide22-6*44 RING DETECTION COUNT[00]|Only applicable if using a 4285/4286 VIP Module and/or if station-initiated d

Page 32 - Mounting the Keypads

Section 22 – Data Field Descriptions22-7*52 STANDARD/EXPANDED REPORT PRIMARYAlm Rst Byp Trbl Opn/Cls Low BattEnter 0 for standard or 1 for expanded re

Page 33 - Installing Symphony (AUI)

VISTA-50PEN Installation and Setup Guide22-8*67 PAGER PHONE NUMBER FOR SUPERVISION| | | | | | | | | | | | | | | |This field is used to enter the alpha

Page 34 - Figure 5-4

Section 22 – Data Field Descriptions22-9*76 PAGER ID NUMBER FOR TESTThis field is used to enter the Pager ID number for Test reports. Enter up to 10

Page 35 - AUI-016-V0

Section 1 – General Description1-3User CodesAccommodates 150 user codes, all of which can operate any or all partitions. Certaincharacteristics must

Page 36 - Programming for Symphony

VISTA-50PEN Installation and Setup Guide22-10*90 SECONDARY SUBSCRIBER ACCT #||||(partition-specific)Enter 00-09; B-F (11-15)[15 15 15 15]Enter the 3-

Page 37

Section 22 – Data Field Descriptions22-111*23 CROSS ZONING PAIR TWO||Enter the second pair of zones, which must both be faulted within a five-minute p

Page 38

VISTA-50PEN Installation and Setup Guide22-121*30 RF RCVR SUPERVISION CHECK-IN INTERVAL[06]|Enter the check-in monitoring interval in 2-hour increment

Page 39 - Figure 6-3

Section 22 – Data Field Descriptions22-131*44 WIRELESS KEYPAD TAMPER DETECT[0]Enter 1 to enable tamper detection on wireless keypad.Enter 0 if tamper

Page 40

VISTA-50PEN Installation and Setup Guide22-141*57 ENABLE 5800 RF BUTTON GLOBAL ARM[0]Enter 1 to have the system arm/disarm in accordance with the butt

Page 41

Section 22 – Data Field Descriptions22-151*76 ACCESS RELAY # # (partition-specific)[00]|The system can be programmed to provide user-activated access

Page 42

VISTA-50PEN Installation and Setup Guide22-162*09 OPEN/CLOSE REPORTS BY EXCEPTION (partition-specific)[0]Enter 1 if Open/Close reports are to be sent

Page 43

Section 22 – Data Field Descriptions22-172*23 DISPLAY BURG & PANIC ALARMS OF OTHER PARTITIONS[0]Enter 1 to allow burglary and panic alarms that oc

Page 44

VISTA-50PEN Installation and Setup Guide22-18

Page 45

23-1 SECTION 23 #93 Menu Mode Programming••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information•••••••••••••••••••••••

Page 46 - Power Up Procedure

VISTA-50PEN Installation and Setup Guide1-4The outputs have the following characteristics:• Can be programmed to activate in response to system event

Page 47 - 128mA maximum

VISTA-50PEN Installation and Setup Guide23-2DEVICE PROG?1 = YES 0 = NOFor defining the following device characteristics for addressabledevices, in

Page 48

24-1 SECTION 24 Scheduling Options••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Introduction to Scheduling♦ Time Window Definitio

Page 49

VISTA-50PEN Installation and Setup Guide24-2Auto-Arm Delay• Auto-arm delay provides a delay (grace period) before auto arming.• It starts at the end o

Page 50

Section 24 – Scheduling Options24-3Exception Reports• This option allows the reporting of openings and closings to the central station only if thearmi

Page 51 - Device Programming

VISTA-50PEN Installation and Setup Guide24-4Scheduling ExampleTo understand scheduling, take, for example, a store that has the following hours:Monday

Page 52 - House ID Sniffer Mode

Section 24 – Scheduling Options24-5Temporary Schedule• The temporary schedule provides a method for the end user to override the daily andholiday sche

Page 53 - 5800 Series Transmitter Setup

VISTA-50PEN Installation and Setup Guide24-6Scheduling Menu ModeThe #80 Scheduling Menu Mode is used to program most of the scheduling and timed-event

Page 54

Section 24 – Scheduling Options24-7Scheduling Menu StructureTo program schedules, enter Scheduling Program Mode:[User Code] + [#] + 80. (Installer or

Page 55

VISTA-50PEN Installation and Setup Guide24-8Time WindowsThe system provides 20 time windows that are defined with start and stop times. Thesewindows

Page 56

Section 24 – Scheduling Options24-9Daily Open/Close SchedulesOpen/Close Schedule WorksheetWrite in the previously defined time window numbers for open

Page 57

Section 1 – General Description1-5Event LogKeeps a log of different event types (enabled in programming). The event log has thefollowing characterist

Page 58 - Menu Mode–Time Driven Events

VISTA-50PEN Installation and Setup Guide24-10Holiday SchedulesA holiday schedule will override the regular daily open/close schedule on the programmed

Page 59 - 121110987654321

Section 24 – Scheduling Options24-11Time-Driven Events WorksheetFill out the worksheet using the steps outlined below.Sched Time Days Action Action Ac

Page 60 - Wiring the 4300 Transformer

VISTA-50PEN Installation and Setup Guide24-12Bypass CommandsActivation times 1 (Beginning), 2 (End), 3 (During) are the only valid choices for bypassc

Page 61 - Programming Output Devices

Section 24 – Scheduling Options24-13Additional CommandsAction Code Action Specifier75 Run Macro Macro #76 Run Script Script #77 Access Point Group Ena

Page 62

VISTA-50PEN Installation and Setup Guide24-14After entering Scheduling Menu Mode, press 0 until the “Timed Events ?” prompt appears.Timed Events ?1 Y

Page 63

Section 24 – Scheduling Options24-15Action Codes: Action Specifier:30=Auto bypass - Zone list31=Auto unbypass - Zone listActions 30-31If actions 30-31

Page 64 - Installing the VIP Module

VISTA-50PEN Installation and Setup Guide24-16Limitation of Access SchedulesLimitation of Access is a means by which a user's access code is limit

Page 65 - Supported by the 4286 only

Section 24 – Scheduling Options24-17Hol A1 Window 2 ?00:00 00:00 00Enter the second time window number for holidays for thisaccess schedule. As the

Page 66 - Installing TeleSmart

VISTA-50PEN Installation and Setup Guide24-18Mon DISARM WIND.00:00AM 00:00AMThis prompt is for entering the start and end times of thedisarm (openin

Page 67 - (CA38A in Canada)

Section 24 – Scheduling Options24-19User Scheduling Menu ModeThe system provides up to 20 "timers" which will be available to the end user f

Page 68 - 8 ohm Speaker

VISTA-50PEN Installation and Setup Guide1-6Built-in User's Manual and Descriptor ReviewFor end-user convenience, the VISTA-50PEN contains a built

Page 69

VISTA-50PEN Installation and Setup Guide24-2006 DAYS? MTWTFSSHIT 0-7 x xTo select the days which are to be activated, enter 1-7(Monday = 1).

Page 70 - 1 2 3 4 5 6

25-1 SECTION 25 System Communication•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Telephone Line Connections♦

Page 71

VISTA-50PEN Installation and Setup Guide25-2A Successful TransmissionWhen a control panel calls the central station receiver, it waits to hear a “hand

Page 72

Section 25 – System Communication25-3Report 3+1/4+1 3+1/4+1 4+2Standard Expanded Low Spd orExpressAlarm SSS(S) A SSS(S) A SSSS AZAAA(A) ZTrouble SSS

Page 73

VISTA-50PEN Installation and Setup Guide25-4ADEMCO High Speed Reporting events by channel:Channels 1 through 8 could have one of the following conditi

Page 74 - Ground Start Operation

Section 25 – System Communication25-5ADEMCO Contact ID Reporting takes the following format:CCCC QEEE GG ZZZ CCCC = Customer (subscriber) IDQ = Event

Page 75 - Remote Keyswitch

VISTA-50PEN Installation and Setup Guide25-6

Page 76

26-1 SECTION 26 Downloading Primer(Remote Downloading is not a UL Listed feature)•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Gen

Page 77 - 7720 WIRING

VISTA-50PEN Installation and Setup Guide26-2Getting On-Line with a Control PanelAt the protected premises, the Control panel must be connected to the

Page 78 - Event Log Printer

Section 26 - Downloading Primer26-3• Shut down all security system functions (non-payment for a leased system)• Inhibit local keypad programming (prev

Page 79

2-1 SECTION 2 Planning a Partitioned System••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Theory of Partitioning♦ Setting Up a Par

Page 80 - Wiring the Long Range Radio

VISTA-50PEN Installation and Setup Guide26-4Remove the alpha numeric pager interface if it is installed while performing the direct-wiredownload. It m

Page 81 - Trouble Messages

27-1 SECTION 27 Setting The Real-Time Clock•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Setting the Time and

Page 82

VISTA-50PEN Installation and Setup Guide27-2

Page 83

28-1 SECTION 28 User Access Codes•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ User Codes & Levels of Aut

Page 84

VISTA-50PEN Installation and Setup Guide28-2Level 0: Installer (User 1) Code• Programmed in field *00 (default = 4-1-4-0). Installer Open/Close repor

Page 85 - OF THIS SYSTEM

Section 28 - User Access Codes28-3Level 6: Duress Codes• Sends a silent alarm to a central monitoring station if the user is being forced to disarm(or

Page 86

VISTA-50PEN Installation and Setup Guide28-4Multiple Partition Access ExamplesEach user is programmed for a primary (home) partition. A user can also

Page 87

Section 28 - User Access Codes28-5Open/Close Rep.?0 = NO , 1 = YESPress 0 (NO) or 1 (YES), depending on whether or notarming/disarming by this user wi

Page 88

VISTA-50PEN Installation and Setup Guide28-6Changing a Master, Manager, or Operator CodeEnter [Installer code]* + 8 + [User number (002-150)] + [new u

Page 89 - User Access Codes

29-1 SECTION 29 Keypad Functions•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Arming Commands♦ Access Control

Page 90

VISTA-50PEN Installation and Setup Guide2-2Setting Up a Partitioned SystemThe basic steps to setting up a partitioned system are described below. If

Page 91

VISTA-50PEN Installation and Setup Guide29-2A user code other than the Installer Code must be programmed into the system in order for theQuick Arm fea

Page 92 - Alarm Output Supervision

Section 29 - Keypad Functions29-3Access ControlThe system has the capability to utilize access control by one of 4 methods.1. One relay may be used fo

Page 93 - 1.7A maximum

VISTA-50PEN Installation and Setup Guide29-4You must program data field 2*18 to enable the GOTO function. This is a partition-specific fieldthat must

Page 94

Section 29 - Keypad Functions29-5For the panic functions to be of practical value, the system must be connected to a central station.Speed Key [D] (Ma

Page 95

VISTA-50PEN Installation and Setup Guide29-6ENTER USER CODE ✴✴✴✴Enter your user code. The programmed Speed Key sequence will be

Page 96 - Programming Event Log Options

Section 29 - Keypad Functions29-7nn DEVICE IS OFFHIT THE "*" KEYVoice: "’VOICE DESCRIPTOR’ DEVICE ‘NN’ ON/OFF. TO EXIT,ENTER 00 NOW&q

Page 97 - Event Logging Procedures

VISTA-50PEN Installation and Setup Guide29-8

Page 98

30-1 SECTION 30 Testing The System•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Battery Test♦ Dialer Test♦ Burglary Walk Test♦ Arm

Page 99

VISTA-50PEN Installation and Setup Guide30-2Armed Burglary System Test• Alarm messages will be sent to the central station during the following tests.

Page 100 - Wiring the 4100APG

Section 30 – Testing The System30-3All partitions containing wireless transmitters must be placed in the test mode for sensitivityreduction of the RF

Page 101

Section 2 – Planning a Partitioned System2-3You cannot select a partition to "arm" the lobby unless it has first been selected to "affe

Page 102 - 4100APG LED Indications

VISTA-50PEN Installation and Setup Guide30-4• "CHECK" accompanied by a numeric display of "8XX," where XX = 00-31, indicates atrou

Page 103 - In This Section

Section 30 – Testing The System30-5Turning the System Over to the User• Fully explain the operation of the system to the user by going over each of it

Page 104 - Connecting the Transformer

VISTA-50PEN Installation and Setup Guide30-6

Page 105 - Programming

A-1APPENDIX A Regulatory Agency Statements•••••••••••••••••••••••••••••••••••••••••••••••••UL Installation RequirementsThe following requirements appl

Page 106

VISTA-50PEN Installation and Setup GuideA-2For Grade AA Service:• You must use a 7920SE Long Range Radio.• Connect the 7920SE to the VISTA-50PEN burgl

Page 107

Appendix A – Regulatory Agency StatementsA-3"FEDERAL COMMUNICATIONS COMMISSION (FCC) STATEMENT"This equipment has been tested to FCC require

Page 108 - Includes 2-wire smoke

VISTA-50PEN Installation and Setup GuideA-4CANADIAN DEPARTMENT OF COMMUNICATIONS(DOC) STATEMENTNOTICEThe Canadian Department of Communications label i

Page 109

B-1APPENDIX B DIP Switch Tables•••••••••••••••••••••••••••••••••••••••••••••••••

Page 110

VISTA-50PEN Installation and Setup GuideB-2DIP SWITCH TABLES FOR ADDRESSABLE POLLING LOOP DEVICES4208 ZONE EXPANDERDIPSHOWN SET FORID 10 (A)SIDE VIEW(

Page 111

Appendix B - DIP Switch TablesB-3DIP SWITCH TABLES FOR POLLING LOOP DEVICES4275 PIRMIRRORDIPSHOWN SET FORID 10 (A)SIDE VIEW(UP)1234567UPDNPOS 6: UP (

Page 113

VISTA-50PEN Installation and Setup Guide2-4In the tables below, the notations in parentheses ( ) indicate the current status of the otherpartition wh

Page 114 - #93 Menu Mode Programming

VISTA-50PEN Installation and Setup GuideB-4

Page 115

C-1APPENDIX C Summary of System Commands••••••••••••••••••••••••••••••••••••••••••••••••••Event LoggingCommandsEvent Log Display = Code + [#] + 60 (In

Page 116

VISTA-50PEN Installation and Setup GuideC-2ProgrammingCommandsSite Initiated Download = User Code + [#] + 1.Direct-Wire Download Enable = User Code +

Page 117 - Wireless Expansion

D-1APPENDIX D Specifications••••••••••••••••••••••••••••••••••••••••••••••••••VISTA-50PEN CONTROLPhysical:14-1/2"W X 18"H X 4.3"DElectr

Page 118

VISTA-50PEN Installation and Setup GuideD-28112; 8122; 8132; 8142 Symphony (AUI)Physical:Width: 7.75 inchesHeight: 8.25 inchesDepth: 1.25 inchesElectr

Page 119

Index-1Index••••••••••••••••••••••••••••••••••••••••••••••••••#70 Relay Mode...29-6#77 Mode...

Page 120 - Zone Type Defaults

VISTA-50PEN Installation and Setup GuideIndex-2Audio Alarm Verification Module Connections...11-2Audio Alarm Verification Programming...

Page 121 - Data Field Descriptions

IndexIndex-3EEarly Power Detect... 13-3Earth Ground Connections...

Page 122 - 95 96 99

VISTA-50PEN Installation and Setup GuideIndex-4LLevel 0 Installer (User 1) Code... 28-2Level 1 Master Codes ...

Page 123

IndexIndex-5POWER UP IN PREVIOUS STATE...18-3, 22-3Powerline Carrier Devices... 9-2Power-Up Proce

Page 124 - (partition-specific)

Section 2 – Planning a Partitioned System2-5Arming/Disarming RemotelyIf arming or disarming remotely (through Compass downloading software), the lobby

Page 125

VISTA-50PEN Installation and Setup GuideIndex-6Timed Events... 24-7Time-Driven Event Program

Page 126

WARNING!THE LIMITATIONS OF THIS ALARM SYSTEMWhile this System is an advanced wireless security system, it does not offer guaranteed protection against

Page 127

ADEMCO LIMITED WARRANTYAlarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions, subsidiaries andaffiliates ("Sel

Page 128

++-N.C.N.C.N.O.2k EOLR(note 1)2k EOLR(note 1)+-+-+-BELLSIRENNO CONNECTIONTRANSFORMER16.5VAC, 40VAADEMCO No.1361(IN CANADAUSE No. 1361CN)or 4300 IF X-1

Page 129 - 95 96 99 Duress

¬.¨lK3271-1BX 9/00165 Eileen Way, Syosset, NY, 11791Copyright  2000 PITTWAY Corporation

Page 130 - [15 15 15 15]

VISTA-50PEN Installation and Setup Guide2-6Additional zone faults will be displayed one at a time. To display a new partition's status,press ✴ +

Page 131

3-1 SECTION 3 False Alarm Reduction Features••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Exit Error Logic a

Page 132

VISTA-50PEN Installation and Setup Guide3-2Exit Delay ResetULThis feature is not suitable for use on a UL commercial burglary installation.This featur

Page 133

Section 3 – False Alarm Reduction Features3-3Call Waiting Defeat LogicAlthough this option does not directly prevent false alarms, it may prevent the

Page 134 - Alm Chck Byps O/C Systm Test

VISTA-50PEN Installation and Setup Guide3-4

Page 135

4-1 SECTION 4 Installing The Control•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Mounting the Control Cabinet♦ Installing the Cab

Page 136 - F B S

VISTA-50PEN Installation and Setup Guide4-2ULTo provide certificated burglary service for UL installations, refer to the special requirements andFigur

Page 137

Section 4 - Installing The Control4-3Grade A Mercantile Safe and Vault ListingFor a Grade A Mercantile Safe and Vault listing, perform the following s

Page 138

iiiTable of Contents••••••••••••••••••••••••••••••••••••••••••••••••••List of Figures...

Page 139

VISTA-50PEN Installation and Setup Guide4-4AC Transformer and BatteryThis product uses the 1361 transformer (1361CN in Canada). We recommend wiring a

Page 140

5-1 SECTION 5 Installing The Keypads•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Keypads That May Be Used♦ Wiring to the Keypads♦

Page 141

VISTA-50PEN Installation and Setup Guide5-2 KEYPADSBLACKREDGREENYELLOWCONTROL TERMINALS 6789Figure 5-1: Keypad Connections to Control Pan

Page 142

Section 5 - Installing The Keypads5-3Addressing the Keypads• The keypads will not operate until they are physically addressed and enabled in the syste

Page 143 - Time Window Definitions

VISTA-50PEN Installation and Setup Guide5-4Prior to attaching the case front to the case back, be sure to wire the Symphony as described inthe "W

Page 144 - Open/Close Definitions

Section 5 - Installing The Keypads5-5AUI-016-V0Figure 5-4: Header ConnectorUnshielded 4-conductor cable is recommended for Symphony power/data wires.

Page 145

VISTA-50PEN Installation and Setup Guide5-6Programming for SymphonySymphonyThe Symphony (AUI) is defaulted to address 01. The VISTA-50PEN has address

Page 146 - Scheduling Menu Mode

6-1 SECTION 6 Basic Hardwired Zones 001-009•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Common Characteristics of Hardwired Zones

Page 147 - Scheduling Menu Structure

VISTA-50PEN Installation and Setup Guide6-2++-N.C.N.C.N.O.2k EOLR 2k EOLR+-++-N.C.N.C.2k EOLR 2k EOLR++-N.C.++-N.C.N.C.2k EOLRSMOKEZone resistance (Ex

Page 148 - Time Windows

Section 6 – Basic Hardwired Zones6-3Wiring 2-wire Smoke DetectorsTo wire 2-wire smoke detectors, perform the following steps:Step Action1 Select from

Page 149 - Daily Open/Close Schedules

Table of ContentsivSECTION 7 2-Wire Polling Loop Expansion...7-1Polling Loop Overview...

Page 150 - Time-Driven Events

VISTA-50PEN Installation and Setup Guide6-4Wiring 4-wire Smoke DetectorsTo wire 4-wire smoke detectors, perform the following steps:Step Action1 Selec

Page 151

Section 6 – Basic Hardwired Zones6-5• The alarm current provided by zone 8 will support only one glassbreak detector in the alarmedstate.• Do not use

Page 152

VISTA-50PEN Installation and Setup Guide6-6

Page 153

7-1 SECTION 7 2-Wire Polling Loop Expansion•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Polling Loop Overview♦ Common Characteris

Page 154

VISTA-50PEN Installation and Setup Guide7-2Compatible Polling Loop Devices4208 8-Zone Expander• Accommodates up to 8 zones via the pollingloop.• DIP s

Page 155 - 50=Off-normal Reminder

Section 7 - 2-Wire Polling Loop Expansion7-3Compatible Polling Loop Devices4101SN Serial Number SingleOutput Relay Module• Form C relay rated at 2A, 2

Page 156

VISTA-50PEN Installation and Setup Guide7-4Wiring Polling Loop DevicesWhen running polling loop wires, they must not be run within 6" of AC power

Page 157 - Temporary Schedules

Section 7 - 2-Wire Polling Loop Expansion7-54190RPM4278PIRPolling loop rating: 128mA maximum. POLLING LOOP21 22 23 24 25+-4192SDSMOKETO RIGHT LOOPFig

Page 158

VISTA-50PEN Installation and Setup Guide7-6CONTROLPANEL429742974297Input PollingLoopNotes: - Do not use 4197 module.- Refer to 4297 instructions for

Page 159 - User Scheduling Menu Mode

8-1 SECTION 8 Wireless Zone Expansion•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Common Characteristics of Wireless Zones♦ RF Sy

Page 160 - 0 = NO,1 = YES 0

Table of ContentsvSECTION 15 External Sounders...15-1General Information...

Page 161

VISTA-50PEN Installation and Setup Guide8-2• Zones 988 and 990 are used to supervise the RF reception of receivers 2 and 1,respectively. The receptio

Page 162 - Reporting Formats

Section 8 – Wireless Zone Expansion8-3Installation and Setup of the 5881 RF ReceiversTo install and setup the 5881 RF Receiver, see to figure 8-1 and

Page 163

VISTA-50PEN Installation and Setup Guide8-4Installing the 5800TM ModuleInstallation of this module is necessary only if you are using one or more 5827

Page 164

Section 8 – Wireless Zone Expansion8-55800 Series Transmitter Setup5800 Series transmitters have built-in serial numbers that must be “learned” by the

Page 165

VISTA-50PEN Installation and Setup Guide8-6Compatible 5800 Series TransmittersModel Product Input Type Description5801 Wireless PanicTransmitterUR or

Page 166

Section 8 – Wireless Zone Expansion8-7Compatible 5800 Series Transmitters (cont’d)Model Product Input Type Description5816 Door/WindowTransmitterRF• H

Page 167

VISTA-50PEN Installation and Setup Guide8-8

Page 168 - On-Line Control Functions

9-1 SECTION 9 Output Devices•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Installing the 4204 and 4204CF Rela

Page 169 - Access Security

VISTA-50PEN Installation and Setup Guide9-2• One class B/style B EOLR-supervised auxiliary input zone.• Operating power and communication with control

Page 170

Section 9 – Output Devices9-3SWITCH 4204 ADDRESS SETTINGSPOSITION ("—" means "OFF")0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 152ON—ON—ON—

Page 171

Table of ContentsviSECTION 24 Scheduling Options...24-1Introduction to Scheduling...

Page 172

VISTA-50PEN Installation and Setup Guide9-4Installing the FSA ModulesThe module will not operate until the device address you have set the DIP switche

Page 173

Section 9 – Output Devices9-5123456789GROUNDGROUNDOUT 6IN 2GROUNDIN 3GROUNDOUT 5J8 CONNECTORBLACKBLUEBROWNGREENREDWHITEYELLOWGRAYVIOLET4142TR CABLE123

Page 174

VISTA-50PEN Installation and Setup Guide9-6ZONE LIST (ZL) is a group of zones to which the “EVENT” applies in order to activatea particular device. N

Page 175

10-1 SECTION 10 Phone Modules•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Installing the VIP Module♦ Install

Page 176 - Enter Auth. Level

VISTA-50PEN Installation and Setup Guide10-2TeleSmartThe TeleSmart system provides a voice interface for an ADEMCO security system and theTeleSmart ph

Page 177

Section 10 – 4285/4286 VIP Module10-3To wire the VIP module, perform the following steps:Step Action1 Make 12V (+) and (–) and data-in and data-out co

Page 178 - To EXIT the User Edit Mode

VISTA-50PEN Installation and Setup Guide10-4If Touch-tones are not present following phone access to the security system via an on-premises phone, try

Page 179

Section 10 – 4285/4286 VIP Module10-5Step ActionConnect keypad wiring as shown (see the chart below for the maximum wire runlength for wire gauge you

Page 180 - 0 = NO , 1 = YES

VISTA-50PEN Installation and Setup Guide10-68 ohm Speaker123456789101112131415161718AUXSPEAKERFigure 10-3: TeleSmart Speaker ConnectionINOUTGRN (DATA

Page 181 - Delaying Closing Time

11-1 SECTION 11 Audio Alarm Verification (AAV) Unit•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ AAV Module O

Page 182 - Panic Keys

Table of ContentsviiSECTION 30 Testing The System ...30-1Battery Test...

Page 183 - Speed Key [D] (Macros)

VISTA-50PEN Installation and Setup Guide11-2One way to trigger the AAV Module is by selecting option 3 in field 1*46 and makeconnections as shown in F

Page 184

Section 11 – Audio Alarm Verification (AAV) Unit11-3CONTROL/DIALER HEADERNOTE:REFER TO AAV MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEAKERS AND M

Page 185 - HIT THE "*" KEY

VISTA-50PEN Installation and Setup Guide11-4• Zone 5 must be programmed for response type 10 and the EOLR must be removed,regardless of whether or not

Page 186

12-1 SECTION 12 J7 Trigger Outputs•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Ground Start Operation♦ Remot

Page 187

VISTA-50PEN Installation and Setup Guide12-2Ground Start OperationULNot intended for use in UL Listed applications..You cannot use Output 1 for an Gro

Page 188 - Testing Wireless Zones

Section 12 – J7 Trigger Outputs12-3Remote Keypad SounderAn optional Amseco PAL 328N Piezo Sounder can be used to duplicate the sounds producedby the k

Page 189 - Trouble Conditions

VISTA-50PEN Installation and Setup Guide12-42K ELOR2K ELORTAMPER SWITCH(CONTACTS CLOSE WHENSWITCH DEPRESSED.LOCK SWITCH(NORMALLY OPEN)+TO J7 / OUT 2TO

Page 190

Section 12 – J7 Trigger Outputs12-5Audio Alarm Verification (AAV) EquipmentAn Audio Alarm Verification (AAV) Module (also known as two-way voice), suc

Page 191 - To the Installer

VISTA-50PEN Installation and Setup Guide12-67920SE RADIOFAU LTZONE 6ZONE 3ZONE 2ZONE 1EARTH GROUND CABINET GROUNDSEE 7920SE INST. INSTR. FORINSTRUCTIO

Page 192

13-1 SECTION 13 Long Range Radio (ECP)•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Wiring the Long Range Rad

Page 193 - Regulatory Agency Statements

viiiList of Figures••••••••••••••••••••••••••••••••••••••••••••••••••Figure 4-1: Installing the Lock...

Page 194 - Requirements

VISTA-50PEN Installation and Setup Guide13-2Additional LRR reporting options are defined by selecting categories of events for eachsubscriber ID in fi

Page 195

Section 13 – 7820 Long Range Radio13-3Trouble MessagesThe following messages will be displayed on the 6139 (alpha keypad) when a problem existsthe Lon

Page 196

VISTA-50PEN Installation and Setup Guide13-4

Page 197 - DIP Switch Tables

14-1 SECTION 14 Access Control•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Access Control Using VistaKey♦ Ac

Page 198

VISTA-50PEN Installation and Setup Guide14-2VistaKey FeaturesVistaKey features are as follows:•Each VistaKey communicates with the VISTA-50PEN via a s

Page 199 - 4278 PIR

Section 14 – Access Control14-3+WEEKLY TESTING IS REQUIREDTO ENSURE PROPER OPERATIONOF THIS SYSTEM.POLE Door Strike/Mag CoilDATA 1 (WHITE)DATA 0

Page 200

VISTA-50PEN Installation and Setup Guide14-4Programming for the VistaKeyThe VISTA-50PEN contains additional programming options in the #93 Menu Mode f

Page 201 - Summary of System Commands

Section 14 – Access Control14-5VistaKey Dialer EnablesWhen the VistaKey is installed with an alarm system, the system defaults are set so that thesyst

Page 202

VISTA-50PEN Installation and Setup Guide14-6}ECHELON NETWORK(PASSPOINT ACS)YELLOWREDBLACKPROM CTRANSFORMER4-PINKEYPADPLUG}TOCONTROL’SKEYPAD TERMINALSG

Page 203 - Specifications

Section 14 – Access Control14-7Using an RF Transmitter ZoneA button type RF button-type transmitter (5804) can be used to provide access or egress for

Page 204

ixConventions Used in This Manual••••••••••••••••••••••••••••••••••••••••••••••••••Before you begin using this manual, it is important that you unders

Page 205

VISTA-50PEN Installation and Setup Guide14-8Using the VISTA-50PEN for Stand-alone Access ControlThe VISTA-50PEN can be used for access control without

Page 206

15-1 SECTION 15 External Sounders•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Alarm Output Supervision♦ Inst

Page 207

VISTA-50PEN Installation and Setup Guide15-2Alarm Output SupervisionWhen supervision is enabled, the panel monitors the alarm output wiring for open a

Page 208

Section 15 – External Sounders15-3Installing Alarm Indicating Devices to the Alarm OutputBe sure to follow the proper guidelines below, depending on w

Page 209

VISTA-50PEN Installation and Setup Guide15-4UL1023 Household Burglary InstallationsFor household burglary installations the total current drawn from t

Page 210

16-1 SECTION 16 Event Log Options•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Event Log Printer Connections♦

Page 211 - WARNING!

VISTA-50PEN Installation and Setup Guide16-2123456789NUJ8 CONNECTORVIOLETGREYYELLOWREDGREENBROWNBLUEBLACKIN 2GROUNDIN 3GROUNDOUT 5OUT 6GROUNDGROUNDPRI

Page 212

Section 16 – Event Log Options16-3Event Logging ProceduresIn order for proper time and date stamping to occur, the system's real-time clock must

Page 213 - SUMMARY OF CONNECTIONS

VISTA-50PEN Installation and Setup Guide16-4ALL EVENT LOGTYPE CCC UUUDisplays all categories of events in chronological order, frommost recent to the

Page 214 - ¬.¨l

17-1 SECTION 17 4100APG Pager Interface•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Mounting the 4100APG♦ Wi

Commentaires sur ces manuels

Pas de commentaire