K3271-1BX 9/0099,,6677$$33((11&RPPHUFLDO%XUJODU\3DUWLWLRQHG6HFXULW\6\VWHPZLWK6FKHGXOLQJ,QVWDOODWLRQDQG6HWXS*XLGH*ARMEDREADYPANICOFF
VISTA-50PEN Installation and Setup Guidex
VISTA-50PEN Installation and Setup Guide17-2Wiring the 4100APGThe 4100APG may be used either with or without a serial printer. The 4100APG connects to
Section 17 – 4100APG Pager Interface17-3With the Event Log PrinterThe serial printer must be configured for 1200 baud rate, seven data bits, even pari
VISTA-50PEN Installation and Setup Guide17-4Programming the Control for the Pager• In field *64 enter 1 to enable the 4100APG pager interface.• In fie
18-1 SECTION 18 Final Power-Up Procedure•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Earth Ground Considerat
VISTA-50PEN Installation and Setup Guide18-2Earth Ground ConsiderationsIn order for the lightning transient protective devices in this product to be e
Section 18 – Final Power-Up Procedure18-3NO CONNECTIONTRANSFORMER16.5VAC, 40VAADEMCO No.1361or 4300, XM10E, orXF10 if X-10 DEVICESWILL BE USED.Connect
VISTA-50PEN Installation and Setup Guide18-4Determining the Control Panel Power Supply LoadUse the following tables to calculate the total current for
Section 18 – Final Power-Up Procedure18-52. In table 2, enter devices used on Auxiliary Power. Calculate standby and alarm currents,then add to get Au
VISTA-50PEN Installation and Setup Guide18-64. In table 4, enter the total calculated subtotals of all listed outputs from Tables 1 through3, then add
Section 18 – Final Power-Up Procedure18-7Battery Capacity Calculation TableUsing the total calculated from Table 4, calculate the battery capacity req
1-1 SECTION 1 General Description••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General♦ Features•••••••••••••••••••••••••••••••••
VISTA-50PEN Installation and Setup Guide18-8
19-1 SECTION 19 The Mechanics of Programming•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Using Data Field Program Mode♦ Entering
VISTA-50PEN Installation and Setup Guide19-2Moving from One Page of Programming to AnotherThe data fields are grouped into four levels (referred to as
Section 19 - The Mechanics of Programming19-3To program system-wide data fields, do the following:Step Action1 Enter Program Mode: [Installer Code] +
VISTA-50PEN Installation and Setup Guide19-4PROGRAMMING PARTITION-SPECIFIC FIELDSPress *91 to select a partition.↓Enter the partition to be programmed
20-1 SECTION 20 Zone Type Definitions•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Zone Number Designations♦ Zone Type Definitions
VISTA-50PEN Installation and Setup Guide20-2Type 02: Entry/Exit #2 BurglaryProvides a secondary entry delay whenever the zone is faulted and the syste
Section 20 – Zone Type Definitions20-3Type 10: Interior with DelayProvides entry and exit delays (using the programmed entry/exit time), if tripped wh
VISTA-50PEN Installation and Setup Guide20-4
21-1 SECTION 21 Zone Index/Zone Type Defaults•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Zone Index♦ Zone Type Defaults•••••••••
VISTA-50PEN Installation and Setup Guide1-2Wireless ExpansionSupports up to 128 wireless zones using 5881 type RF receiver (fewer if using hardwireand
VISTA-50PEN Installation and Setup Guide21-2Zone Type DefaultsFollowing are the zone type defaults for zones on the VISTA-50PEN:Zone # Zone Type Zone
22-1 SECTION 22 Data Field Descriptions•••••••••••••••••••••••••••••••••••••••••••••••••The following is a description of all data fields provided by
VISTA-50PEN Installation and Setup Guide22-2*14 ZONE 9 RESPONSE TIME[0]Enter 1 to set fast response mode (10 msec) for appropriate devices wired to zo
Section 22 – Data Field Descriptions22-3*23 MULTIPLE ALARMS (partition-specific)[1]Determines whether or not more than one alarm can be sounded in a
VISTA-50PEN Installation and Setup Guide22-4*30 TOUCHTONE OR ROTARY DIAL[0]Enter 1 if TouchTone service is being used.Enter 0 if rotary phone service
Section 22 – Data Field Descriptions22-5*37 DOWNLOAD COMMAND ENABLESDialerShutdownSystemShutdownNotUsedRemoteBypassRemoteDisarmRemoteArmUploadProgramD
VISTA-50PEN Installation and Setup Guide22-6*44 RING DETECTION COUNT[00]|Only applicable if using a 4285/4286 VIP Module and/or if station-initiated d
Section 22 – Data Field Descriptions22-7*52 STANDARD/EXPANDED REPORT PRIMARYAlm Rst Byp Trbl Opn/Cls Low BattEnter 0 for standard or 1 for expanded re
VISTA-50PEN Installation and Setup Guide22-8*67 PAGER PHONE NUMBER FOR SUPERVISION| | | | | | | | | | | | | | | |This field is used to enter the alpha
Section 22 – Data Field Descriptions22-9*76 PAGER ID NUMBER FOR TESTThis field is used to enter the Pager ID number for Test reports. Enter up to 10
Section 1 – General Description1-3User CodesAccommodates 150 user codes, all of which can operate any or all partitions. Certaincharacteristics must
VISTA-50PEN Installation and Setup Guide22-10*90 SECONDARY SUBSCRIBER ACCT #||||(partition-specific)Enter 00-09; B-F (11-15)[15 15 15 15]Enter the 3-
Section 22 – Data Field Descriptions22-111*23 CROSS ZONING PAIR TWO||Enter the second pair of zones, which must both be faulted within a five-minute p
VISTA-50PEN Installation and Setup Guide22-121*30 RF RCVR SUPERVISION CHECK-IN INTERVAL[06]|Enter the check-in monitoring interval in 2-hour increment
Section 22 – Data Field Descriptions22-131*44 WIRELESS KEYPAD TAMPER DETECT[0]Enter 1 to enable tamper detection on wireless keypad.Enter 0 if tamper
VISTA-50PEN Installation and Setup Guide22-141*57 ENABLE 5800 RF BUTTON GLOBAL ARM[0]Enter 1 to have the system arm/disarm in accordance with the butt
Section 22 – Data Field Descriptions22-151*76 ACCESS RELAY # # (partition-specific)[00]|The system can be programmed to provide user-activated access
VISTA-50PEN Installation and Setup Guide22-162*09 OPEN/CLOSE REPORTS BY EXCEPTION (partition-specific)[0]Enter 1 if Open/Close reports are to be sent
Section 22 – Data Field Descriptions22-172*23 DISPLAY BURG & PANIC ALARMS OF OTHER PARTITIONS[0]Enter 1 to allow burglary and panic alarms that oc
VISTA-50PEN Installation and Setup Guide22-18
23-1 SECTION 23 #93 Menu Mode Programming••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information•••••••••••••••••••••••
VISTA-50PEN Installation and Setup Guide1-4The outputs have the following characteristics:• Can be programmed to activate in response to system event
VISTA-50PEN Installation and Setup Guide23-2DEVICE PROG?1 = YES 0 = NOFor defining the following device characteristics for addressabledevices, in
24-1 SECTION 24 Scheduling Options••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Introduction to Scheduling♦ Time Window Definitio
VISTA-50PEN Installation and Setup Guide24-2Auto-Arm Delay• Auto-arm delay provides a delay (grace period) before auto arming.• It starts at the end o
Section 24 – Scheduling Options24-3Exception Reports• This option allows the reporting of openings and closings to the central station only if thearmi
VISTA-50PEN Installation and Setup Guide24-4Scheduling ExampleTo understand scheduling, take, for example, a store that has the following hours:Monday
Section 24 – Scheduling Options24-5Temporary Schedule• The temporary schedule provides a method for the end user to override the daily andholiday sche
VISTA-50PEN Installation and Setup Guide24-6Scheduling Menu ModeThe #80 Scheduling Menu Mode is used to program most of the scheduling and timed-event
Section 24 – Scheduling Options24-7Scheduling Menu StructureTo program schedules, enter Scheduling Program Mode:[User Code] + [#] + 80. (Installer or
VISTA-50PEN Installation and Setup Guide24-8Time WindowsThe system provides 20 time windows that are defined with start and stop times. Thesewindows
Section 24 – Scheduling Options24-9Daily Open/Close SchedulesOpen/Close Schedule WorksheetWrite in the previously defined time window numbers for open
Section 1 – General Description1-5Event LogKeeps a log of different event types (enabled in programming). The event log has thefollowing characterist
VISTA-50PEN Installation and Setup Guide24-10Holiday SchedulesA holiday schedule will override the regular daily open/close schedule on the programmed
Section 24 – Scheduling Options24-11Time-Driven Events WorksheetFill out the worksheet using the steps outlined below.Sched Time Days Action Action Ac
VISTA-50PEN Installation and Setup Guide24-12Bypass CommandsActivation times 1 (Beginning), 2 (End), 3 (During) are the only valid choices for bypassc
Section 24 – Scheduling Options24-13Additional CommandsAction Code Action Specifier75 Run Macro Macro #76 Run Script Script #77 Access Point Group Ena
VISTA-50PEN Installation and Setup Guide24-14After entering Scheduling Menu Mode, press 0 until the “Timed Events ?” prompt appears.Timed Events ?1 Y
Section 24 – Scheduling Options24-15Action Codes: Action Specifier:30=Auto bypass - Zone list31=Auto unbypass - Zone listActions 30-31If actions 30-31
VISTA-50PEN Installation and Setup Guide24-16Limitation of Access SchedulesLimitation of Access is a means by which a user's access code is limit
Section 24 – Scheduling Options24-17Hol A1 Window 2 ?00:00 00:00 00Enter the second time window number for holidays for thisaccess schedule. As the
VISTA-50PEN Installation and Setup Guide24-18Mon DISARM WIND.00:00AM 00:00AMThis prompt is for entering the start and end times of thedisarm (openin
Section 24 – Scheduling Options24-19User Scheduling Menu ModeThe system provides up to 20 "timers" which will be available to the end user f
VISTA-50PEN Installation and Setup Guide1-6Built-in User's Manual and Descriptor ReviewFor end-user convenience, the VISTA-50PEN contains a built
VISTA-50PEN Installation and Setup Guide24-2006 DAYS? MTWTFSSHIT 0-7 x xTo select the days which are to be activated, enter 1-7(Monday = 1).
25-1 SECTION 25 System Communication•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Telephone Line Connections♦
VISTA-50PEN Installation and Setup Guide25-2A Successful TransmissionWhen a control panel calls the central station receiver, it waits to hear a “hand
Section 25 – System Communication25-3Report 3+1/4+1 3+1/4+1 4+2Standard Expanded Low Spd orExpressAlarm SSS(S) A SSS(S) A SSSS AZAAA(A) ZTrouble SSS
VISTA-50PEN Installation and Setup Guide25-4ADEMCO High Speed Reporting events by channel:Channels 1 through 8 could have one of the following conditi
Section 25 – System Communication25-5ADEMCO Contact ID Reporting takes the following format:CCCC QEEE GG ZZZ CCCC = Customer (subscriber) IDQ = Event
VISTA-50PEN Installation and Setup Guide25-6
26-1 SECTION 26 Downloading Primer(Remote Downloading is not a UL Listed feature)•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Gen
VISTA-50PEN Installation and Setup Guide26-2Getting On-Line with a Control PanelAt the protected premises, the Control panel must be connected to the
Section 26 - Downloading Primer26-3• Shut down all security system functions (non-payment for a leased system)• Inhibit local keypad programming (prev
2-1 SECTION 2 Planning a Partitioned System••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Theory of Partitioning♦ Setting Up a Par
VISTA-50PEN Installation and Setup Guide26-4Remove the alpha numeric pager interface if it is installed while performing the direct-wiredownload. It m
27-1 SECTION 27 Setting The Real-Time Clock•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Setting the Time and
VISTA-50PEN Installation and Setup Guide27-2
28-1 SECTION 28 User Access Codes•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ User Codes & Levels of Aut
VISTA-50PEN Installation and Setup Guide28-2Level 0: Installer (User 1) Code• Programmed in field *00 (default = 4-1-4-0). Installer Open/Close repor
Section 28 - User Access Codes28-3Level 6: Duress Codes• Sends a silent alarm to a central monitoring station if the user is being forced to disarm(or
VISTA-50PEN Installation and Setup Guide28-4Multiple Partition Access ExamplesEach user is programmed for a primary (home) partition. A user can also
Section 28 - User Access Codes28-5Open/Close Rep.?0 = NO , 1 = YESPress 0 (NO) or 1 (YES), depending on whether or notarming/disarming by this user wi
VISTA-50PEN Installation and Setup Guide28-6Changing a Master, Manager, or Operator CodeEnter [Installer code]* + 8 + [User number (002-150)] + [new u
29-1 SECTION 29 Keypad Functions•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Arming Commands♦ Access Control
VISTA-50PEN Installation and Setup Guide2-2Setting Up a Partitioned SystemThe basic steps to setting up a partitioned system are described below. If
VISTA-50PEN Installation and Setup Guide29-2A user code other than the Installer Code must be programmed into the system in order for theQuick Arm fea
Section 29 - Keypad Functions29-3Access ControlThe system has the capability to utilize access control by one of 4 methods.1. One relay may be used fo
VISTA-50PEN Installation and Setup Guide29-4You must program data field 2*18 to enable the GOTO function. This is a partition-specific fieldthat must
Section 29 - Keypad Functions29-5For the panic functions to be of practical value, the system must be connected to a central station.Speed Key [D] (Ma
VISTA-50PEN Installation and Setup Guide29-6ENTER USER CODE ✴✴✴✴Enter your user code. The programmed Speed Key sequence will be
Section 29 - Keypad Functions29-7nn DEVICE IS OFFHIT THE "*" KEYVoice: "’VOICE DESCRIPTOR’ DEVICE ‘NN’ ON/OFF. TO EXIT,ENTER 00 NOW&q
VISTA-50PEN Installation and Setup Guide29-8
30-1 SECTION 30 Testing The System•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Battery Test♦ Dialer Test♦ Burglary Walk Test♦ Arm
VISTA-50PEN Installation and Setup Guide30-2Armed Burglary System Test• Alarm messages will be sent to the central station during the following tests.
Section 30 – Testing The System30-3All partitions containing wireless transmitters must be placed in the test mode for sensitivityreduction of the RF
Section 2 – Planning a Partitioned System2-3You cannot select a partition to "arm" the lobby unless it has first been selected to "affe
VISTA-50PEN Installation and Setup Guide30-4• "CHECK" accompanied by a numeric display of "8XX," where XX = 00-31, indicates atrou
Section 30 – Testing The System30-5Turning the System Over to the User• Fully explain the operation of the system to the user by going over each of it
VISTA-50PEN Installation and Setup Guide30-6
A-1APPENDIX A Regulatory Agency Statements•••••••••••••••••••••••••••••••••••••••••••••••••UL Installation RequirementsThe following requirements appl
VISTA-50PEN Installation and Setup GuideA-2For Grade AA Service:• You must use a 7920SE Long Range Radio.• Connect the 7920SE to the VISTA-50PEN burgl
Appendix A – Regulatory Agency StatementsA-3"FEDERAL COMMUNICATIONS COMMISSION (FCC) STATEMENT"This equipment has been tested to FCC require
VISTA-50PEN Installation and Setup GuideA-4CANADIAN DEPARTMENT OF COMMUNICATIONS(DOC) STATEMENTNOTICEThe Canadian Department of Communications label i
B-1APPENDIX B DIP Switch Tables•••••••••••••••••••••••••••••••••••••••••••••••••
VISTA-50PEN Installation and Setup GuideB-2DIP SWITCH TABLES FOR ADDRESSABLE POLLING LOOP DEVICES4208 ZONE EXPANDERDIPSHOWN SET FORID 10 (A)SIDE VIEW(
Appendix B - DIP Switch TablesB-3DIP SWITCH TABLES FOR POLLING LOOP DEVICES4275 PIRMIRRORDIPSHOWN SET FORID 10 (A)SIDE VIEW(UP)1234567UPDNPOS 6: UP (
VISTA-50PEN Installation and Setup Guide2-4In the tables below, the notations in parentheses ( ) indicate the current status of the otherpartition wh
VISTA-50PEN Installation and Setup GuideB-4
C-1APPENDIX C Summary of System Commands••••••••••••••••••••••••••••••••••••••••••••••••••Event LoggingCommandsEvent Log Display = Code + [#] + 60 (In
VISTA-50PEN Installation and Setup GuideC-2ProgrammingCommandsSite Initiated Download = User Code + [#] + 1.Direct-Wire Download Enable = User Code +
D-1APPENDIX D Specifications••••••••••••••••••••••••••••••••••••••••••••••••••VISTA-50PEN CONTROLPhysical:14-1/2"W X 18"H X 4.3"DElectr
VISTA-50PEN Installation and Setup GuideD-28112; 8122; 8132; 8142 Symphony (AUI)Physical:Width: 7.75 inchesHeight: 8.25 inchesDepth: 1.25 inchesElectr
Index-1Index••••••••••••••••••••••••••••••••••••••••••••••••••#70 Relay Mode...29-6#77 Mode...
VISTA-50PEN Installation and Setup GuideIndex-2Audio Alarm Verification Module Connections...11-2Audio Alarm Verification Programming...
IndexIndex-3EEarly Power Detect... 13-3Earth Ground Connections...
VISTA-50PEN Installation and Setup GuideIndex-4LLevel 0 Installer (User 1) Code... 28-2Level 1 Master Codes ...
IndexIndex-5POWER UP IN PREVIOUS STATE...18-3, 22-3Powerline Carrier Devices... 9-2Power-Up Proce
Section 2 – Planning a Partitioned System2-5Arming/Disarming RemotelyIf arming or disarming remotely (through Compass downloading software), the lobby
VISTA-50PEN Installation and Setup GuideIndex-6Timed Events... 24-7Time-Driven Event Program
WARNING!THE LIMITATIONS OF THIS ALARM SYSTEMWhile this System is an advanced wireless security system, it does not offer guaranteed protection against
ADEMCO LIMITED WARRANTYAlarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions, subsidiaries andaffiliates ("Sel
++-N.C.N.C.N.O.2k EOLR(note 1)2k EOLR(note 1)+-+-+-BELLSIRENNO CONNECTIONTRANSFORMER16.5VAC, 40VAADEMCO No.1361(IN CANADAUSE No. 1361CN)or 4300 IF X-1
¬.¨lK3271-1BX 9/00165 Eileen Way, Syosset, NY, 11791Copyright 2000 PITTWAY Corporation
VISTA-50PEN Installation and Setup Guide2-6Additional zone faults will be displayed one at a time. To display a new partition's status,press ✴ +
3-1 SECTION 3 False Alarm Reduction Features••••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Exit Error Logic a
VISTA-50PEN Installation and Setup Guide3-2Exit Delay ResetULThis feature is not suitable for use on a UL commercial burglary installation.This featur
Section 3 – False Alarm Reduction Features3-3Call Waiting Defeat LogicAlthough this option does not directly prevent false alarms, it may prevent the
VISTA-50PEN Installation and Setup Guide3-4
4-1 SECTION 4 Installing The Control•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Mounting the Control Cabinet♦ Installing the Cab
VISTA-50PEN Installation and Setup Guide4-2ULTo provide certificated burglary service for UL installations, refer to the special requirements andFigur
Section 4 - Installing The Control4-3Grade A Mercantile Safe and Vault ListingFor a Grade A Mercantile Safe and Vault listing, perform the following s
iiiTable of Contents••••••••••••••••••••••••••••••••••••••••••••••••••List of Figures...
VISTA-50PEN Installation and Setup Guide4-4AC Transformer and BatteryThis product uses the 1361 transformer (1361CN in Canada). We recommend wiring a
5-1 SECTION 5 Installing The Keypads•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Keypads That May Be Used♦ Wiring to the Keypads♦
VISTA-50PEN Installation and Setup Guide5-2 KEYPADSBLACKREDGREENYELLOWCONTROL TERMINALS 6789Figure 5-1: Keypad Connections to Control Pan
Section 5 - Installing The Keypads5-3Addressing the Keypads• The keypads will not operate until they are physically addressed and enabled in the syste
VISTA-50PEN Installation and Setup Guide5-4Prior to attaching the case front to the case back, be sure to wire the Symphony as described inthe "W
Section 5 - Installing The Keypads5-5AUI-016-V0Figure 5-4: Header ConnectorUnshielded 4-conductor cable is recommended for Symphony power/data wires.
VISTA-50PEN Installation and Setup Guide5-6Programming for SymphonySymphonyThe Symphony (AUI) is defaulted to address 01. The VISTA-50PEN has address
6-1 SECTION 6 Basic Hardwired Zones 001-009•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Common Characteristics of Hardwired Zones
VISTA-50PEN Installation and Setup Guide6-2++-N.C.N.C.N.O.2k EOLR 2k EOLR+-++-N.C.N.C.2k EOLR 2k EOLR++-N.C.++-N.C.N.C.2k EOLRSMOKEZone resistance (Ex
Section 6 – Basic Hardwired Zones6-3Wiring 2-wire Smoke DetectorsTo wire 2-wire smoke detectors, perform the following steps:Step Action1 Select from
Table of ContentsivSECTION 7 2-Wire Polling Loop Expansion...7-1Polling Loop Overview...
VISTA-50PEN Installation and Setup Guide6-4Wiring 4-wire Smoke DetectorsTo wire 4-wire smoke detectors, perform the following steps:Step Action1 Selec
Section 6 – Basic Hardwired Zones6-5• The alarm current provided by zone 8 will support only one glassbreak detector in the alarmedstate.• Do not use
VISTA-50PEN Installation and Setup Guide6-6
7-1 SECTION 7 2-Wire Polling Loop Expansion•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Polling Loop Overview♦ Common Characteris
VISTA-50PEN Installation and Setup Guide7-2Compatible Polling Loop Devices4208 8-Zone Expander• Accommodates up to 8 zones via the pollingloop.• DIP s
Section 7 - 2-Wire Polling Loop Expansion7-3Compatible Polling Loop Devices4101SN Serial Number SingleOutput Relay Module• Form C relay rated at 2A, 2
VISTA-50PEN Installation and Setup Guide7-4Wiring Polling Loop DevicesWhen running polling loop wires, they must not be run within 6" of AC power
Section 7 - 2-Wire Polling Loop Expansion7-54190RPM4278PIRPolling loop rating: 128mA maximum. POLLING LOOP21 22 23 24 25+-4192SDSMOKETO RIGHT LOOPFig
VISTA-50PEN Installation and Setup Guide7-6CONTROLPANEL429742974297Input PollingLoopNotes: - Do not use 4197 module.- Refer to 4297 instructions for
8-1 SECTION 8 Wireless Zone Expansion•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Common Characteristics of Wireless Zones♦ RF Sy
Table of ContentsvSECTION 15 External Sounders...15-1General Information...
VISTA-50PEN Installation and Setup Guide8-2• Zones 988 and 990 are used to supervise the RF reception of receivers 2 and 1,respectively. The receptio
Section 8 – Wireless Zone Expansion8-3Installation and Setup of the 5881 RF ReceiversTo install and setup the 5881 RF Receiver, see to figure 8-1 and
VISTA-50PEN Installation and Setup Guide8-4Installing the 5800TM ModuleInstallation of this module is necessary only if you are using one or more 5827
Section 8 – Wireless Zone Expansion8-55800 Series Transmitter Setup5800 Series transmitters have built-in serial numbers that must be “learned” by the
VISTA-50PEN Installation and Setup Guide8-6Compatible 5800 Series TransmittersModel Product Input Type Description5801 Wireless PanicTransmitterUR or
Section 8 – Wireless Zone Expansion8-7Compatible 5800 Series Transmitters (cont’d)Model Product Input Type Description5816 Door/WindowTransmitterRF• H
VISTA-50PEN Installation and Setup Guide8-8
9-1 SECTION 9 Output Devices•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Installing the 4204 and 4204CF Rela
VISTA-50PEN Installation and Setup Guide9-2• One class B/style B EOLR-supervised auxiliary input zone.• Operating power and communication with control
Section 9 – Output Devices9-3SWITCH 4204 ADDRESS SETTINGSPOSITION ("—" means "OFF")0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 152ON—ON—ON—
Table of ContentsviSECTION 24 Scheduling Options...24-1Introduction to Scheduling...
VISTA-50PEN Installation and Setup Guide9-4Installing the FSA ModulesThe module will not operate until the device address you have set the DIP switche
Section 9 – Output Devices9-5123456789GROUNDGROUNDOUT 6IN 2GROUNDIN 3GROUNDOUT 5J8 CONNECTORBLACKBLUEBROWNGREENREDWHITEYELLOWGRAYVIOLET4142TR CABLE123
VISTA-50PEN Installation and Setup Guide9-6ZONE LIST (ZL) is a group of zones to which the “EVENT” applies in order to activatea particular device. N
10-1 SECTION 10 Phone Modules•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Installing the VIP Module♦ Install
VISTA-50PEN Installation and Setup Guide10-2TeleSmartThe TeleSmart system provides a voice interface for an ADEMCO security system and theTeleSmart ph
Section 10 – 4285/4286 VIP Module10-3To wire the VIP module, perform the following steps:Step Action1 Make 12V (+) and (–) and data-in and data-out co
VISTA-50PEN Installation and Setup Guide10-4If Touch-tones are not present following phone access to the security system via an on-premises phone, try
Section 10 – 4285/4286 VIP Module10-5Step ActionConnect keypad wiring as shown (see the chart below for the maximum wire runlength for wire gauge you
VISTA-50PEN Installation and Setup Guide10-68 ohm Speaker123456789101112131415161718AUXSPEAKERFigure 10-3: TeleSmart Speaker ConnectionINOUTGRN (DATA
11-1 SECTION 11 Audio Alarm Verification (AAV) Unit•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ AAV Module O
Table of ContentsviiSECTION 30 Testing The System ...30-1Battery Test...
VISTA-50PEN Installation and Setup Guide11-2One way to trigger the AAV Module is by selecting option 3 in field 1*46 and makeconnections as shown in F
Section 11 – Audio Alarm Verification (AAV) Unit11-3CONTROL/DIALER HEADERNOTE:REFER TO AAV MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEAKERS AND M
VISTA-50PEN Installation and Setup Guide11-4• Zone 5 must be programmed for response type 10 and the EOLR must be removed,regardless of whether or not
12-1 SECTION 12 J7 Trigger Outputs•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Ground Start Operation♦ Remot
VISTA-50PEN Installation and Setup Guide12-2Ground Start OperationULNot intended for use in UL Listed applications..You cannot use Output 1 for an Gro
Section 12 – J7 Trigger Outputs12-3Remote Keypad SounderAn optional Amseco PAL 328N Piezo Sounder can be used to duplicate the sounds producedby the k
VISTA-50PEN Installation and Setup Guide12-42K ELOR2K ELORTAMPER SWITCH(CONTACTS CLOSE WHENSWITCH DEPRESSED.LOCK SWITCH(NORMALLY OPEN)+TO J7 / OUT 2TO
Section 12 – J7 Trigger Outputs12-5Audio Alarm Verification (AAV) EquipmentAn Audio Alarm Verification (AAV) Module (also known as two-way voice), suc
VISTA-50PEN Installation and Setup Guide12-67920SE RADIOFAU LTZONE 6ZONE 3ZONE 2ZONE 1EARTH GROUND CABINET GROUNDSEE 7920SE INST. INSTR. FORINSTRUCTIO
13-1 SECTION 13 Long Range Radio (ECP)•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Wiring the Long Range Rad
viiiList of Figures••••••••••••••••••••••••••••••••••••••••••••••••••Figure 4-1: Installing the Lock...
VISTA-50PEN Installation and Setup Guide13-2Additional LRR reporting options are defined by selecting categories of events for eachsubscriber ID in fi
Section 13 – 7820 Long Range Radio13-3Trouble MessagesThe following messages will be displayed on the 6139 (alpha keypad) when a problem existsthe Lon
VISTA-50PEN Installation and Setup Guide13-4
14-1 SECTION 14 Access Control•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Access Control Using VistaKey♦ Ac
VISTA-50PEN Installation and Setup Guide14-2VistaKey FeaturesVistaKey features are as follows:•Each VistaKey communicates with the VISTA-50PEN via a s
Section 14 – Access Control14-3+WEEKLY TESTING IS REQUIREDTO ENSURE PROPER OPERATIONOF THIS SYSTEM.POLE Door Strike/Mag CoilDATA 1 (WHITE)DATA 0
VISTA-50PEN Installation and Setup Guide14-4Programming for the VistaKeyThe VISTA-50PEN contains additional programming options in the #93 Menu Mode f
Section 14 – Access Control14-5VistaKey Dialer EnablesWhen the VistaKey is installed with an alarm system, the system defaults are set so that thesyst
VISTA-50PEN Installation and Setup Guide14-6}ECHELON NETWORK(PASSPOINT ACS)YELLOWREDBLACKPROM CTRANSFORMER4-PINKEYPADPLUG}TOCONTROL’SKEYPAD TERMINALSG
Section 14 – Access Control14-7Using an RF Transmitter ZoneA button type RF button-type transmitter (5804) can be used to provide access or egress for
ixConventions Used in This Manual••••••••••••••••••••••••••••••••••••••••••••••••••Before you begin using this manual, it is important that you unders
VISTA-50PEN Installation and Setup Guide14-8Using the VISTA-50PEN for Stand-alone Access ControlThe VISTA-50PEN can be used for access control without
15-1 SECTION 15 External Sounders•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Alarm Output Supervision♦ Inst
VISTA-50PEN Installation and Setup Guide15-2Alarm Output SupervisionWhen supervision is enabled, the panel monitors the alarm output wiring for open a
Section 15 – External Sounders15-3Installing Alarm Indicating Devices to the Alarm OutputBe sure to follow the proper guidelines below, depending on w
VISTA-50PEN Installation and Setup Guide15-4UL1023 Household Burglary InstallationsFor household burglary installations the total current drawn from t
16-1 SECTION 16 Event Log Options•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Event Log Printer Connections♦
VISTA-50PEN Installation and Setup Guide16-2123456789NUJ8 CONNECTORVIOLETGREYYELLOWREDGREENBROWNBLUEBLACKIN 2GROUNDIN 3GROUNDOUT 5OUT 6GROUNDGROUNDPRI
Section 16 – Event Log Options16-3Event Logging ProceduresIn order for proper time and date stamping to occur, the system's real-time clock must
VISTA-50PEN Installation and Setup Guide16-4ALL EVENT LOGTYPE CCC UUUDisplays all categories of events in chronological order, frommost recent to the
17-1 SECTION 17 4100APG Pager Interface•••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Mounting the 4100APG♦ Wi
Commentaires sur ces manuels