Vue de la page 40
4-1
SECTION 4
Programming
•••••••••••••••••••••••••••••••••••••••••••••••••
Program Modes
There are two programming modes for the VISTA-
50P/VISTA-50PUL. These are the Data Field Program
Mode and the #93 Menu Mode. The Data Field Program
Mode is where many system options are programmed.
The #93 Menu Mode is an interactive mode that
requires a 2-line alpha keypad (6139/6160).
The factory-loaded defaults (97) enable
keypad addresses 00-01 only. A keypad set to
one of these addresses must be used to
program the system initially.
Local keypad programming can be disabled
throu
g
h Compass downloadin
g
software. If this
is done, Program mode can only be accessed
via the downloading software.
Entering and Exiting Programming Mode
Enter Programming mode using either method a or b:
a. Press both the [] and [#] keys at the same time
within 30 seconds after power is applied to the
control.
b. Enter the Installer Code + [8] + [0] + [0] keys.
The factory installer code can be changed once in
the Program mode (field 00).
NOTE: The default for the Installer Code is 4140.
Exit the Programming mode by either method a or b:
a. Press [] + [9] + [8]. Exiting by this method
prevents the installer code from being used to re-
enter Programming mode. Only method “a” can be
used to re-enter Programming mode.
b. Press [] + [9] + [9]. Exiting by this method
permits the installer code to be being used to re-
enter Programming mode.
Data Field Programming Mode
In the Data Field Program Mode you may access any
field simply by entering either [] or [#] + the field
number:
To write or change information in a field press []
+ the field number (03).
To read the information in a field press [#] + the
field number (#03).
When the entries for a field are completed, the keypad
beeps three times and advances to the next field.
Summary of Data Field Programming Commands
91
Select partition for programming partition-specific fields
92
Display the software revision level of the control panel
93
Enter Menu mode programming
94
Go to next page of fields
99
Go back to previous page of fields or exit
Programming Mode with no installer code lockout
98
Exit Programming Mode with Installer Code lockout
Moving Between Programming Levels
The data fields are grouped into three levels (referred to
as “pages”). The first page is accessed as soon as
Programming Mode is entered.
The second and third pages of data fields are indicated
at the keypad by a 1 and 2, respectively, in front of the
2-digit field address. “ALT PROGRAM MODE” is
displayed along with a “100” or “200,” indicating which
page of program fields is accessed.
To access the next level of programming fields, perform
the following steps:
Step Action
1
Press 94.
2 Press [] + [XX], where XX = the last two
digits of the program field, and make the
desired entry.
NOTES:
Press 94 to move to 2nd page, (fields 101 - 176);
press 99 to move back to 1st page.
Press 94 to move to 3rd page (fields 200 - 221);
press 99 to move back to 2nd page
Entry Errors
If an address is improperly entered, the keypad
displays “FC.”
If a program entry is improperly entered (for
example, a larger number than is permitted), the
keypad display will go blank.
In either of the above cases, simply re-enter [] + the
correct field number and then enter the correct data.