N6019-2V1 1/98VISTA-100COMMERCIAL FIRE AND BURGLARYPARTITIONED SECURITY SYSTEMwith SCHEDULINGINSTALLATION INSTRUCTIONSandPROGRAMMING GUIDE
xHow To Use This ManualThis manual is written to accommodate both the new and the experienced installer ofADEMCO products. The information contained i
18-1SECTION 18The Mechanics Of Programming••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Using Data Field Program Mode♦ System and C
VISTA-100 Installation Instructions18-2Entering Data Field Programming ModeEnter Data Field Program Mode using one of these methods:• Press both the ✴
Section 18 - The Mechanics of Programming18-3• In either of the above cases, simply re-enter ✴ plus the correct field number.SUMMARY OF DATA FIELD PR
VISTA-100 Installation Instructions18-4you have finished entering the partition-specific fields, enter the number of any globalfield.Repeat Steps 1 an
19-1SECTION 19Zone Type Definitions••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Zone Number Designations♦ Zone Type Definitions•••
VISTA-100 Installation Instructions19-2Type 02: Entry/Exit #2 BurglaryThis zone type provides a secondary entry delaywhenever the zone is faulted if y
Section 19 - Zone Type Definitions19-3response. Initial short detection causes 6-secondsmoke detector power reset. A subsequent shortdetection withi
VISTA-100 Installation Instructions19-4
20-1SECTION 20Zone Index/Zone Type Defaults••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Zone Index♦ Zone Type Defaults••••••••••••
VISTA-100 Installation Instructions20-2Zone Type DefaultsThe following tables detail the zone type defaults for zones on the VISTA-100:Zone # Zone Typ
xiConventions Used in This ManualBefore you begin using this manual, it is important that you understand the meaning of thefollowing symbols (icons).N
21-1SECTION 21 Data Field Descriptions••••••••••••••••••••••••••••••••••••••••••••••••The following is a description of all data fields provided by t
VISTA-100 Installation Instructions21-2*13 BELL 1 TIMEOUT (partition-specific) [04]|This field defines the length of time Bell Output 1 and the keyp
Section 21 - Data Field Descriptions21-3*22 KEYPAD PANIC ENABLES (partition-specific) [001]||995 996 999Enter 1 to enable the appropriate keypad pani
VISTA-100 Installation Instructions21-429 QUICK ARM (partition-specific) [0]If you enable Quick Arm, the user can arm the burglary system in AWAY, S
Section 21 - Data Field Descriptions21-5Enter the downloading phone number, up to 17 digits (the same as in fields *33 and*34). Do not fill unused sp
VISTA-100 Installation Instructions21-6*44 RING DETECTION COUNT[00]|This field is only applicable if you are using a 4285/4286 VIP Module and/or if yo
Section 21 - Data Field Descriptions21-7option 3, fire alarms and supervisories go to the primary number only; all reports go tothe secondary number.*
VISTA-100 Installation Instructions21-8*88 BURG. ALARM COMM. DELAY (partition-specific)[0]Enter 0 if you want no delay on burglary alarm communicatio
Section 21 - Data Field Descriptions21-91*23 CROSS ZONING PAIR TWO||||Enter the second pair of zones that must both be faulted within a 5-minute perio
VISTA-100 Installation Instructions21-101*33 TOUCHTONE W/ROTARY BACKUP[0]Enter 1 to enable rotary backup dialing if the communicator is not successfu
VISTA-100 Installation Instructions1-xiiSECTION 1General Description••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Overview♦
Section 21 - Data Field Descriptions21-111*53 DISABLE DOWNLOAD CALLBACK[0]Enter 1 to disable the callback requirement for downloading. Enter 0 to requ
VISTA-100 Installation Instructions21-12command "57." (Refer to Section 22: #93 Menu Mode Programming and “Programmingwith #80 Scheduling Me
Section 21 - Data Field Descriptions21-13suppressed during the closing window in order to prevent false alarms if the user armsthe system, then re-ent
VISTA-100 Installation Instructions21-142*24 DISPLAY TROUBLES OF OTHER PARTITIONS[0]Enter 1 if you want troubles that occur on other partitions to be
Section 21 - Data Field Descriptions21-153*21 MAX # OF DIALER RETRIES[8]Enter a number from 1 to 8 to set the maximum number of retries to each teleph
VISTA-100 Installation Instructions21-163*60 BELL 2 & AUX RELAY TIMEOUT[00,00]|| Bell 2 Aux. Rly.Use this field to define the length of time Bel
22-1SECTION 22#93 Menu Mode Programming••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦#93 Main Menu Options♦ Zone Programming♦ Storin
VISTA-100 Installation Instructions22-2pre-programmed).SEQUENTIAL LEARN?0=No 1=YesOn the Sequential Learn Menu, you can perform thesefunctions:• Progr
Section 22 - #93 Menu Mode Programming22-3#93 Menu Mode Key Commands#93 Enters Menu Mode. ✴ Serves as ENTER key. Press to have keypad accept the
VISTA-100 Installation Instructions22-4ENTER ZN NO.000 = QUIT 010Zone 010 entered ↑ Enter the 3-digit zone number that you want to program. Asan examp
Section 1 - General Description1-xiii• Individually assignable to bell outputs and/or aux. relayULWireless devices are not permitted in UL Commercial
Section 22 - #93 Menu Mode Programming22-5Press ✴ to continue.010 BELL/RLY SEL 0Assign each zone to activate either one or both bell outputsand/or
VISTA-100 Installation Instructions22-6Figure 22-1: RF Transmitter Loop Designations010 LEARN S/N?1 = YES, 0 = NO 1If the device’s serial number has
Section 22 - #93 Menu Mode Programming22-7010 INPUT S/N A022-4064The system will enroll the serial number of the first deviceheard and will displa
VISTA-100 Installation Instructions22-8To enroll serial numbers in Sequential Mode, take the following steps:1. Enter Data Field Programming Mode by e
Section 22 - #93 Menu Mode Programming22-9If the first zone number you enter does not have all of the aboveattributes, the system will search its data
VISTA-100 Installation Instructions22-10At any time during this step, you may press ✴ on the keypad or the upper left button of theprogram tool if yo
Section 22 - #93 Menu Mode Programming22-11To enter report codes, take the following steps:Enter Program Mode by entering [Installer Code] + 8 0 0 0.
VISTA-100 Installation Instructions22-12double-digit entry) and press ✴ . The second digit will bethe ID (second) digit of the Alarm report code for
Section 22 - #93 Menu Mode Programming22-13enter other system report codes, enter 0 (NO) and press ✴ tocontinue.System Group 3 CodesSYSTEM GROUP #3?1
VISTA-100 Installation Instructions22-14• Each description can be composed of a combination of words (up to 3) that are selectedfrom a vocabulary of 2
VISTA-100 Installation Instructions1-xiv• Certain system options are selectable for each partition, such as Entry/Exit Delay andsubscriber account num
Section 22 - #93 Menu Mode Programming22-15Find the descriptor words you want to use in the fixed-word vocabulary list later in thissection. In this e
VISTA-100 Installation Instructions22-2a. Press [#], followed by the 2-digit code that represents the first letter you would like todisplay (e.g., 65
Section 22 - #93 Menu Mode Programming22-3A cursor will be present at the extreme left of the first line (over the first asterisk). Press6 to move the
VISTA-100 Installation Instructions22-4ALPHA DESCRIPTOR VOCABULARYUse this vocabulary list to enter alpha descriptors. To select a word, press [#] fo
Section 22 - #93 Menu Mode Programming22-5Device ProgrammingUse this menu to program keypads, receivers, and relay modules.From Data Field Programming
VISTA-100 Installation Instructions22-6SOUND OPTIONIf you entered device type 1 (alpha keypad), this prompt willappear. You can program keypads indiv
Section 22 - #93 Menu Mode Programming22-7START (STT) The START programming determines when and under what conditionsthe device will be activated. Th
VISTA-100 Installation Instructions22-8B)1. ZONE TYPE/SYSTEM OPERATION (ZT). Instead of using aRESTORE ZONE LIST, you can select a specific zone (resp
Section 22 - #93 Menu Mode Programming22-902 START: ZN TYPEYou can use a Zone Type/System Operation instead of or inaddition to an Event/Zone List com
VISTA-100 Installation Instructions22-1001 FIRE BELL?1 = YES 0 = NOIf this relay is on a supervised 4204CF module, you can use itas an additional fir
Section 1 - General Description1-xvAuxiliary RelayProvides a built-in Form C relay which can be used for one of the following purposes:• Alarm activat
Section 22 - #93 Menu Mode Programming22-11001 Zn to Delete?000=QUIT 000Enter each zone number to be deleted from the Zone List,pressing ✴ af
VISTA-100 Installation Instructions22-12Relay Voice Descriptors and Custom Word Substitutes VocabularyWord IndexAir...116Ala
Section 22 - #93 Menu Mode Programming22-1301 ENTER INDEX #Enter the 3-digit substitute word index number from the RelayVoice Descriptors and Custom
23-1SECTION 23Scheduling Options••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Introduction to Scheduling♦ Time Window Definitions♦
VISTA-100 Installation Instructions23-2friendly menus (#80, #81 & #83 modes), explained in detail in this section. These menustake you step by ste
Section 23 - Scheduling Options23-3Time-DrivenEventsBy using time windows, the system can automatically activate and de-activate relays at predetermin
VISTA-100 Installation Instructions23-4Mon Tue Wed Thu Fri Sat Sun HolOp/Cl Op/Cl Op/Cl Op/Cl Op/Cl Op/Cl Op/Cl Op/Cl01/04 01/04 01/04 01/04 01/05 02/
Section 23 - Scheduling Options23-5Open/Close DefinitionsOpening and closing windows are controlled by schedules that you define. There are threetypes
VISTA-100 Installation Instructions23-6Programming with #80 Scheduling Menu ModeYou can use #80 Scheduling Menu Mode to program most of the scheduling
Section 23 - Scheduling Options23-7There are 5 sets of scheduling menus, as shown below. To select a menu set, enter 1 at adisplayed main menu prompt.
VISTA-100 Installation Instructions1-xviOptional Backup DialerSupports use of 5140DLM Backup Dialer for connecting to a second supervised telephonelin
VISTA-100 Installation Instructions23-8Time Windows Definitions WorksheetThe system provides 20 time windows that you can define with start and stop t
Section 23 - Scheduling Options23-9Time Window programming and display the “Quit?” prompt.Enter 0 at the “Quit?” prompt toreturn to the main menu choi
VISTA-100 Installation Instructions23-10Open/Close Schedules programming. You will see the “Quit?”prompt.Enter 0 at the “Quit?” prompt toreturn to the
Section 23 - Scheduling Options23-11Holiday Definitions & Schedule WorksheetYou can define up to 16 holidays for the system. Each holiday can be a
VISTA-100 Installation Instructions23-12When you have programmed all holidays, enter 00 at the“HOLIDAY NUMBER?” prompt to exit the Holiday menus.Time-
Section 23 - Scheduling Options23-13Relay commandsAction CodeActionSpecifier01 Relay On Relay #02 Relay Off Relay #03 Relay Close for 2 seconds Rel
VISTA-100 Installation Instructions23-14Open/Close WindowsActivation time 3 (During) is the only valid choice for these functions:Action CodeActionSpe
Section 23 - Scheduling Options23-15Timed Events?1 Yes 0 = No 0Enter 1 to program timed events using relay outputs.TIMED EVENT # ?01-20, 00=Q
VISTA-100 Installation Instructions23-16time that has been stored for the window is displayed. Pressthe ✴ to continue.01 Active time?
Section 23 - Scheduling Options23-17Access Sched. ?1 Yes 0 = No 0Enter 1 to program access schedules.If no limitations apply, enter 0.ACCESS S
Section 1 - General Description1-xviiCross-Zoning CapabilityHelps prevent false alarms by preventing a zone from going into alarm unless its designate
VISTA-100 Installation Instructions23-18Partition/Windows Mon Tue Wed Thu Fri Sat SunStart Time HH:MMStop Time HH:MM3Disarm WindowStart Time HH:MMStop
Section 23 - Scheduling Options23-19Programming Temporary SchedulesOnly users with an authority level of manager or higher can program temporary sched
VISTA-100 Installation Instructions23-20#83 User Scheduling Menu ModeThe system provides up to 20 "timers" that allow the end user to contro
Section 23 - Scheduling Options23-21Enter 0 to put the schedule in effect for one week only.Press ✴ to accept the entry. The system will quit UserSc
24-1SECTION 24System Communication••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ A Successful Transmission♦ Reporting Formats♦ Loadi
VISTA-100 Installation Instructions24-2The following table describes each format in greater detail:3+1 and 4+1 StandardFormatsComprised of a 3- or 4-d
Section 24 - System Communications24-3ADEMCO Contact ID Reporting takes the following format: CCCC QEEE GG ZZZwher
VISTA-100 Installation Instructions24-41234 5155 1555 1 (Acct #1234, with alarms on channels 9 and 12)LIMITATIONS• ADEMCO High Speed reporting provide
Section 24 - System Communications24-5TABLE OF CONTACT ID EVENT CODESCode Definition110 Fire Alarm111 Smoke Alarm*113 Water Flow Alarm121 Duress122 Si
VISTA-100 Installation Instructions24-6COMMUNICATION DEFAULTS for LOW SPEED FORMAT (*94*80)*45 PRIMARY FORMAT 0 Ademco Low Speed*46 LOW SPEED FOR
2-1SECTION 2Planning a Partitioned System••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Theory of Partitioning♦ Setting Up a Partiti
Section 24 - System Communications24-7COMMUNICATION DEFAULTS FOR ZONESZone #Low Speed1st 2ndExpress1st 2ndHigh Speed1st 2ndContact ID1st 2nd001 01 00
VISTA-100 Installation Instructions24-8COMMUNICATION DEFAULTS FOR ZONES (cont’d)Zone #Low Speed1st 2ndExpress1st 2ndHigh Speed1st 2ndContact ID1st 2nd
Section 24 - System Communications24-9COMMUNICATION DEFAULTS FOR ZONES (cont’d)Zone #Low Speed1st 2ndExpress1st 2ndHigh Speed1st 2ndContact ID1st 2nd6
VISTA-100 Installation Instructions24-10COMMUNICATION DEFAULTS FOR ZONES (cont’d)Zone #Low Speed1st 2ndExpress1st 2ndHigh Speed1st 2ndContact ID1st 2n
25-1SECTION 25Downloading Primer(Remote Downloading is not a UL Listed feature)••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Genera
VISTA-100 Installation Instructions25-22. Enter [Installer code] + [#] + 5. The panel temporarily enables a ring count of 5 andsets the Download Callb
Section 25 - Downloading Primer25-3• Set the real-time clock.Access SecurityAccess to the control panel from a remote location is protected against co
VISTA-100 Installation Instructions25-4The connections between the control panel and the 4100SM are different from thoseshown in the 4100SM Installati
26-1SECTION 26Setting The Real-Time Clock••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Setting the Time and Da
VISTA-100 Installation Instructions26-2
VISTA-100 Installation Instructions2-2(multiple access) can "log on" to one partition from another partition's keypad, providedthat pro
27-1SECTION 27User Access Codes••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ User Codes and Levels of Authorit
VISTA-100 Installation Instructions27-2Level 0: Installer (User 1)• Program this level in field *00 (default = 5-1-4-0). Select installer Open/Close r
VISTA-100 Installation Instructions27-2• Operator C (sometimes known as the Babysitter code) cannot disarm the system unlessthe system was armed with
Section 27 - User Access Codes27-3Note that Open/Close reporting of Quick Arm is enabled if User 002 is enabled forOpen/Close reporting, and that Quic
VISTA-100 Installation Instructions27-4User Number = 003Enter Auth. LevelEnter the level number as follows:1 = Master (arm, disarm, bypass, add, or mo
Section 27 - User Access Codes27-5global arm options that you programmed for each partition towhich you granted the user access. For example:Part. 1 A
28-1SECTION 28Keypad Functions••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Arming Functions♦ Global Arming♦ A
VISTA-100 Installation Instructions28-2SYSTEM COMMANDSFUNCTION ACTIONDisplay FaultedZonesBefore arming, the system must be in the READY condition (all
Section 28 - Keypad Functions28-3• If, when you are disarming the system using a Global Disarm, any of the selectedpartitions has a condition that wou
VISTA-100 Installation Instructions28-4Part. 1 A0T WHSEUser 01 Auth.=1G.The user's Open/Close report capability is shown by the periodfollowing
iiRecommendations for Proper ProtectionThe Following Recommendations For The Location Of Fire And Burglary Detection Devices Help ProvideProper Covera
Section 2 - Planning a Partitioned System2-3You cannot program a partition to "arm" the lobby unless you first program it to "affect&qu
Section 28 - Keypad Functions28-5• Arming sequences that involve bypassing certain zones before arming.• Seldom-used but repeatable sequences.• Relay
VISTA-100 Installation Instructions28-6nn DEVICE IS OFFHIT 0=OFF , 1=ONVoice: "[voice descriptor] DEVICE nn ON/OFF. FOR [voicedescriptor] ON E
29-1SECTION 29Testing The System••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Checkout Procedure for Hardwired Zones♦ Checkout Proc
VISTA-100 Installation Instructions29-2to which the zone is assigned should display the number of the faulted zone. Trippingfire and panic zones will
Section 29 - Testing The System29-35. When you see the proper display on the keypad(s), the polling loop zones in the systemare functioning properly
VISTA-100 Installation Instructions29-4• If you are using a single receiver, the keypad will beep three times to indicate that ithas received a signal
Section 29 - Testing The System29-5by the installer by entering [Installer Code] + [#] + 68 while the burglary portion of thesystem is disarmed. This
VISTA-100 Installation Instructions29-6Burglary Walk-Test (Code + TEST 5)The Burglary Walk-Test causes the system to sound keypad beeps in response to
Section 29 - Testing The System29-7Trouble ConditionsSupervisory MessagesA keypad display of “SUPV” accompanied by a zone number (001-087) and an alph
VISTA-100 Installation Instructions29-8• Fire trouble on any zone (zone response types 9, 16, 17, 18, 19)• Fire supervisory present (zone response typ
VISTA-100 Installation Instructions2-4Sequence #2:Office 1 Office 2 Lobby ActionUser #2:(Armed) Disarms DisarmsUser #1:Disarms (Disarmed) (No change)U
Section 29 - Testing The System29-9Contacting Technical SupportPLEASE!Before you call Technical Support, be sure you:• READ THE INSTRUCTIONS!• Check a
VISTA-100 Installation Instructions29-10
Appendix A-1APPENDIX ARegulatory Agency Statements••••••••••••••••••••••••••••••••••••••••••••••••UL Installation RequirementsThe following requiremen
VISTA-100 Installation InstructionsAppendix A-2• If a secondary number is programmed, set the maximum number of dialer re-tries to 3, 4,or 5 in field
Appendix A - Regulatory Agency StatementsAppendix A-3For Grade AA Service:• Follow the instructions for Grade A service, except use the 7920SE in plac
VISTA-100 Installation InstructionsAppendix A-4"FEDERAL COMMUNICATIONS COMMISSION (FCC) STATEMENT"This equipment has been tested to FCC requ
Appendix A - Regulatory Agency StatementsAppendix A-5CANADIAN DEPARTMENT OF COMMUNICATIONS(DOC) STATEMENTNOTICEThe Canadian Department of Communicatio
VISTA-100 Installation InstructionsAppendix A-6
Appendix B-1APPENDIX BDIP Switch Tables••••••••••••••••••••••••••••••••••••••••••••••••
Section 2 - Planning a Partitioned System2-5Master Keypad Setup and OperationAlthough this system has 8 actual partitions, it provides an extra partit
Appendix B - DIP Switch TablesAppendix B-3DIP SWITCH TABLES FOR POLLING LOOP DEVICES4275 PIRMIRRORDIPSHOWN SET FORID 10 (A)SIDE VIEW(UP)1234567UPDNPOS
VISTA-100 Installation InstructionsAppendix B-4DIP SWITCH TABLES FOR 5700 RF SYSTEM WIRELESS DEVICESHOUSE ID (1 SHOWN)HOUSE ID (1 SHOWN)HOUSE ID (1 SH
Appendix C-1APPENDIX CSummary of System Commands••••••••••••••••••••••••••••••••••••••••••••••••Event LoggingCommandsEvent Log Display = Code + [#] +
VISTA-100 Installation InstructionsAppendix C-2SchedulingCommandsInstaller-Programmed Schedule Events = Installer Code + [#] + 80Temporary Schedule Ed
Appendix D-1APPENDIX DSpecifications••••••••••••••••••••••••••••••••••••••••••••••••VISTA-100 CONTROLPhysical:18”H X 14.5”W X 4.3”DElectrical:Primary
VISTA-100 Installation InstructionsAppendix D-2DIGITAL COMMUNICATORFormats Supported:ADEMCO High SpeedADEMCO 4+2 ExpressADEMCO Low SpeedADEMCO Contact
Index-1Index••••••••••••••••••••••••••••••••••••••••••••••••1451 Enclosure, 4-41451 Transformer, 4-424-Hour Audible Alarm, 19-224-Hour Auxiliary Alarm
VISTA-100 Installation InstructionsIndex-2FFalse Alarm Reduction, 3-1FCC, A-4FCC Registration No, D-1Federal CommunicationsCommission (FCC) Statement,
IndexIndex-3TTamper Protection, 8-7Technical Support: Contact, 29-9Telephone Line Connections,15-1Temporary Schedule Worksheet,23-18Temporary Schedule
VISTA-100 Installation InstructionsIndex-4
VISTA-100 Installation Instructions2-6A Master keypad uses the same panic buttons as Partition 1. Master keypad panics are sent toPartition 1, and wi
WARNING!THE LIMITATIONS OF THIS ALARM SYSTEMWhile this System is an advanced wireless security system, it does not offer guaranteed protection against
Appendix-6We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and theirloved ones to learn about t
ADEMCO LIMITED WARRANTYAlarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions, subsidiariesand affiliates ("Sel
TRANSFORMERW/ENCLOSUREADEMCO No.1451(supplied)INPUT: 120VAC, 60HZ, 1.0A max. Connect to a dedicated circuit. See
165 Eileen Way, Syosset, New York, 11791Copyright © 1997 PITTWAY CORPORATION
3-1SECTION 3False Alarm Reduction Features••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Exit Error Logic and R
VISTA-100 Installation Instructions3-2• Exit Error by Zone (this is sent as a regular alarm if you are using ADEMCO High Speedformat)• Bypass reportsR
Section 3 - False Alarm Reduction Features3-3• If an entry/exit zone is paired with an interior follower zone, be sure to enter theentry/exit zone as
VISTA-100 Installation Instructions3-4
4-1SECTION 4Installing The Control••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Mounting the Control Cabinet♦ Installing the Cabine
VISTA-100 Installation Instructions4-2ULFor UL installations which are intended to provide certificated burglary service, refer to thespecial requirem
iiiIn addition, we recommend that radio backup be used in a security system so that alarm signals canstill be sent to the alarm monitoring station in
Section 4 - Installing The Control4-3Installing the Control's Circuit BoardTo install the control’s circuit board, take the following steps and r
VISTA-100 Installation Instructions4-4Panel Earth Ground ConnectionsTo ground the panel, take the following steps:1. Connect the earth ground post ins
5-1SECTION 5Installing The Keypads••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Keypads That May Be Used♦ Wiring to the Keypads♦ Us
VISTA-100 Installation Instructions5-2• The length of all wire runs combined must not exceed 2000 feet when unshielded quadconductor cable is used (10
Section 5 - Installing The Keypads5-3Figure 5-2. Using a Supplementary Power Supply for KeypadsMounting the KeypadsMount the keypads at a height that
VISTA-100 Installation Instructions5-45. When the proper “READY” message is displayed on the keypad(s) addressed at 00, 01, 02,and 03, the system is f
6-1SECTION 6Basic Hardwired Zones 001-008••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Common Characteristics of Hardwired Zones 1-
VISTA-100 Installation Instructions6-2Wiring 2-Wire Smoke Detectors to Zones 1 and 2Zones 1 and 2 have the added capability of supporting 2-wire smoke
Section 6 - Basic Hardwired Zones 001-0086-3Compatible 2-Wire Smoke DetectorsYou may use up to sixteen 2-wire smoke detectors each on zones 1 and 2. T
VISTA-100 Installation Instructions6-4Figure 6-2. 4-Wire Smoke Detector Connections (Zones 1-8)2. Connect detectors (including heat detectors, if use
ivTable of Contents••••••••••••••••••••••••••••••••••••••••••••••••RECOMMENDATIONS FOR PROPER PROTECTION...
Section 6 - Basic Hardwired Zones 001-0086-5When you set it in this manner, the zone will trigger a trouble when the panel is disarmedand an alarm whe
VISTA-100 Installation Instructions6-6Programming and Checkout of Hardwired ZonesYou must program each zone in order for it to become operational. To
7-1SECTION 72-Wire Polling Loop Expansion(Zones 9 - 87)••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Polling Loop Overview♦ Common
VISTA-100 Installation Instructions7-2number or group is determined by the setting of DIP switches. Other devices have a built-inunique serial number
Section 7 - 2-Wire Polling Loop Expansion7-3Figure 7-1. Polling Loop ConnectionsThe 4297 Polling Loop Extender may be used to provide additional poll
VISTA-100 Installation Instructions7-4Figure 7-2a. Polling Loop Connections Using One 4297 Extender ModuleFigure 7-2b. Polling Loop Connections Usin
Section 7 - 2-Wire Polling Loop Expansion7-5Polling Loop SupervisionA short on the polling loop is indicated by a trouble on its supervisory zone, and
VISTA-100 Installation Instructions7-6Compatible Polling Loop Devices (cont’d)4275 Dual PIR • Dual-element PIR with built-in RPM(connects directly to
8-1SECTION 8Wireless Zone Expansion••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Common Characteristics of Wireless Zones♦ Wireless
VISTA-100 Installation Instructions8-25800 SeriesReceiver Zones5881L up to 85881M up to 165881H up to 875881EH up to 87 (use withUL864 installations)I
Table of ContentsvFire Alarm Verification for Smoke Detectors...6-4Zone 6 Tamper Configu
Section 8 - Wireless Zone Expansion8-3• For maximum range, install the RF receiver at least 10 feet from the control panel orany keypads to avoid inte
VISTA-100 Installation Instructions8-4Installing the 5800TM ModuleYou will need to install this module only if you are using one or more 5827BD Wirele
Section 8 - Wireless Zone Expansion8-55700 Series Transmitter SetupEach 5700 Series transmitter has DIP switches to set both the transmitter’s zone nu
VISTA-100 Installation Instructions8-6Zone Type Trans/Zone #Entry/Exit Burglary 1 through 47 *Perimeter Burglary 1 through 47 *Interior Burglary 1 thr
Section 8 - Wireless Zone Expansion8-7Compatible 5700 Series Transmitters (cont’d)Model Product Zone No. Description5775 PIR Detector 32-47 • Dual-ele
VISTA-100 Installation Instructions8-8The supervision for a particular transmitter that may be carried off the premises (5801,5802MN) can be turned of
Section 8 - Wireless Zone Expansion8-9Compatible 5800 Series Transmitters (cont’d)Model ProductProgram AsInput Type Description58025802CPPendant (Pers
VISTA-100 Installation Instructions8-10Compatible 5800 Series Transmitters (cont’d)Model ProductProgram AsInput Type Description5827 Wireless Keypad H
8-1SECTION 9Relay Outputs••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Relay Basics♦ Wiring the 4204 and 4204CF Relay Modules♦ Prog
VISTA-100 Installation Instructions9-2Figure 9-1a: 4204 Relay ModuleSWITCH 4204 ADDRESS SETTINGSPOSITION ("—" means "OFF")0 1 2 3
Table of ContentsviSection 13. EXTERNAL SOUNDERS... 13-1Ge
Section 9-Relay Outputs9-3Figure 9-1b: 4204CF Relay Module3. When you are mounting them remotely, homerun each module back to the control. Thetable be
VISTA-100 Installation Instructions9-4
10-1SECTION 104285/4286 VIP Module••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Mounting the VIP Module♦ Wirin
VISTA-100 Installation Instructions10-2To mount the VIP Module, take the following steps:1. When the VIP Module is mounted inside the control cabinet,
Section 10-4285 VIP Module10-3ANSWERING MACHINESPEAKER VOLUMEADJUSTABLE ON4286 ONLY▲▲4285/4286PHONE MODULE123456 7YELLOW: TO DATA OUT (term. 14)NO CON
VISTA-100 Installation Instructions10-4
11-1SECTION 11Audio Alarm Verification (AAV) Unit••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ AAV Module Oper
VISTA-100 Installation Instructions11-2messages triggered during ongoing conversation will be held until either the AAV modulesignals that it is inact
Section 11 – Audio Alarm Verification (AAV) Unit11-31 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16▲ONMODEL EAGLE SECURITY1241REFER TO AAV MODULEINSTRUC
VISTA-100 Installation Instructions11-4
Table of ContentsviiReport Code Programming...22-9Programmin
12-1SECTION 12J2 Trigger Outputs••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Remote Keypad Sounder Operation
VISTA-100 Installation Instructions12-2Figure 12-1. J2 Pin Assignments and FunctionsRemote Keypad Sounder Operation and WiringYou can use an optional
Figure 12-3. Remote Keyswitch WiringULIn Commercial Fire installations, mount the keyswitch next to a keypad. The keypad will providethe UL-required
VISTA-100 Installation Instructions12-4Keyswitch Operation With Alarms Present:A momentary short across zone 7 will silence alarm bell and keypad soun
Section 12 – J2 Trigger Outputs12-5If you use this feature, set program field 3*20 to 2, and connect the 5140LED module toJ2/OUT 1, 3, 4, 5, as shown
VISTA-100 Installation Instructions12-6The fire and burglary/audible panic alarm triggers remain HIGH until a [User Code] + OFFis entered in all enabl
4.7K(NOTE)ZONE 1TB212345678910TB112345678910CONNECT TO POLLINGLOOP GROUND SCREWZONE 2ZONE 3ZONE 4ZONE 5FAULTCABINET GROUNDEARTH GROUNDSEE 7920SE INST.
VISTA-100 Installation Instructions12-8Event Log Printer ConnectionsThe VISTA-100's event log can be printed on a local serial printer. If you u
Section 12 – J2 Trigger Outputs12-9
13-1SECTION 13External Sounders••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Bell Circuit Supervision♦ Program
Table of ContentsviiiTo Add an RF Key to an Existing User...27-6To DELETE a Mas
VISTA-100 Installation Instructions13-2To unsupervise bell circuits, take the following steps:1. Cut the white jumpers W1 (for Bell 1) and/or W4 (for
Section 13 - External Sounders13-3ModelDescriptionSystem Sensor MASS121575 ADA Horn/StrobeSystem Sensor MA/SS-12 Horn/StrobeWheelock LS1-12-VFR Strobe
14-1SECTION 14Auxiliary Relay••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Relay Functions•••••••••••••••••••••••••••••••••••••••••
VISTA-100 Installation Instructions14-2Trouble/Supervisory Activation (3*61 = 0)You can program steady activation in response to any zone- or system-r
Section 14- Auxiliary Relay14-3
15-1SECTION 15Dialer Outputs••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Dialer Outputs Available♦ Telephone Line Connections♦ Tel
VISTA-100 Installation Instructions15-2• To prevent the risk of shock, disconnect phone lines at telco jacks before servicing the panel.• If the commu
Section 15- Dialer Outputs15-3
16-1SECTION 16Event Log Options••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ General Information♦ Event Log Printer Connections♦ Pr
VISTA-100 Installation Instructions16-2123456789J2 CONNECTOR4142TR CABLE876543214100SM+ PWR- (GND)RXDnot usednot usednot usednot usedDTRRED BLUE WH
ixList of Figures••••••••••••••••••••••••••••••••••••••••••••••••4-1. Installing the Lock...
Section 16- Event Log Options16-55. Exit Program Mode by pressing *99.NOTE: For more information about actual programming procedures, see Section 18:
VISTA-100 Installation Instructions16-4ALL EVENT LOGTYPE CCC UUUDisplay shows all categories of events in chronological orderfrom most recent to oldes
Section 16- Event Log Options16-5
17-1SECTION 17Final Power-Up Procedure••••••••••••••••••••••••••••••••••••••••••••••••In This Section♦ Connecting the AC Transformer♦ Backup Power Cal
VISTA-100 Installation Instructions17-25. Replace the front cover of the enclosure and fasten it with the screws supplied.A few seconds after power is
Section 17 – Final Power-Up17-3Select one of the batteries (listed in the Battery Selection Table later in this section)which has a capacity greater t
VISTA-100 Installation Instructions17-4Total Control Panel Load WorksheetsTo calculate the total current for the Aux. Power 1, Aux. Power 2, Bell 1 an
Section 17 – Final Power-Up17-55. Enter the total pollingloop using valuescalculated in thepolling loopworksheet.POLLING LOOP Total CurrentStandby Ala
VISTA-100 Installation Instructions17-6Capacity Formula Calc ValueStandbyCapacityTotal standby load x 24 or 60 hours x 1.1contingency factor (use tota
Section 17 – Final Power-Up17-7
Commentaires sur ces manuels