- 3 -
/<1;/<1 ;5
DATA FIELDS
Field Function Programmed Values [ ] = Table 1 Default Values
SYSTEM SETUP (
20–
30)
20
INSTALLER CODE
[4112]
Enter 4 digits, 0–9
21
QUICK ARM ENABLE
[1]
0 = no; 1 = yes
22
KEYPAD BACKLIGHT TIMEOUT
[0]
0 = none (backlighting always on); 1 = backlight off after 10secs
23
FORCED BYPASS
[0]
0 = none; 1 = bypass open zones
UL installations = 0
24
RF HOUSE ID CODE
|
[00]
00 = disable all wireless keypad usage;
01–31 = 5827/5827BD/5804BD house ID
25
POWERLINE CARRIER DEVICE
[0]
HOUSE CODE
0 = A; 1 = B, 2 = C, 3 = D, 4 = E, 5 = F, 6 = G, 7 = H, 8 = I, 9 =
J, #10 = K, #11 = L, #12 = M, #13 = N, #14 = O, #15 = P
26
CHIME BY ZONE
[1]
0 = no; 1 = yes (program zones to chime on zone list 3)
27
REAL TIME CLOCK DISPLAY
[1]
0 = no; 1 = yes, display time on keypad
29
DAYLIGHT SAVING TIME
[4, 10]
START/END MONTH Start End
1-9, #+10,#+11,#+12. Enter 0,0 if no daylight savings time used.
30
DAYLIGHT SAVING TIME
[1,5]
START/END WEEKEND Start End
0 = disable; 1=first; 2=second; 3=third; 4=fourth;
5=last; 6=next to last; 7=third from last
ZONE SOUNDS AND TIMING (
31–
39)
31
SINGLE ALARM SOUNDING/ZONE
[0]
1 = yes, limit once per arming period (also applies to long range
radio output if “0” is selected in *91 field); 0 = no limit;
UL installations = 0
32
FIRE SOUNDER TIMEOUT
[0]
0 = timeout; 1 = no timeout
33
ALARM BELL TIMEOUT
[1]
0 = none; 1=4 min; 2=8 min; 3=12 min; 4 = 16 min;
UL installations = 1 (4 min) minimum
Entry of a number other than one specified will give unpredictable results.