-7-
––––––––––––––––– ZONE RESPONSE TYPE CHARACTERISTICS ––––––––––––––––––
Zone Response Type Characteristics
1 – Entry/Exit Burglary Provides exit delay time when panel is armed in any arming mode.
Provides entry delay when panel is armed in Away and Stay modes
only.
3 – Perimeter Burglary Provides an instant alarm when panel is armed in any arming mode.
4 – Interior, Follower Provides exit delay time when panel is armed in any mode.
Will only provide entry delay if an Entry/Exit zone is faulted first upon
entry. Otherwise, alarm will be instant.
Bypassed automatically when panel is armed in the Stay or Instant
mode.
5 – Trouble by Day/Alarm by
Night
Provides a trouble response if panel is not armed when zone is faulted.
Provides an instant alarm if panel is armed in any mode.
6 – 24-Hr. Silent Alarm Provides a silent alarm to Central Station whether panel is armed or
disarmed.
7 – 24 Hr. Audible Alarm Provides an audible alarm at the bell output and keypad whether
panel is armed or disarmed.
8 – 24-Hr. Auxiliary Alarm Provides an audible alarm at the keypad only. No bell output is
provided.
9 – Fire Provides a fire alarm when zone is shorted. Causes bell output to
pulse.
Provides a trouble response when zone is open.
10 – Interior w/Delay Provides entry and exit delay times.
Bypassed automatically when panel is armed in the Stay or Instant
mode.
–––––––––––––––––––––––––––WIRING GUIDELINES ––––––––––––––––––––––––––––
Wiring Run Chart For Devices* Drawing Aux Power From
The Control (12V+ & GND)
TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE
RUN
Wire Size 50 mA or less 100 mA 300 mA 500 mA
#22 500 ft (152m) 250 ft (76m) 80 ft (24m) 50 ft (15m)
#20 750 ft (228.6m) 380 ft (116m) 130 ft (39.6m) 80 ft (24m)
#18 1300 ft (396m) 650 ft (198m) 220 ft (67m) 130 ft (39.6m)
#16 1500 ft (457m) 1000 ft (305m) 330 ft (100.5m) 200 ft (70m)
* Includes Keypads and alarm devices requiring separate power.
Example: If you have two motion detectors that draw a total of 44 mA, and you are using #20 AWG
wire, the distance from the control panel Aux + and - terminals to the last device can be up
to 750 ft.
IMPORTANT
The length of all wire runs for keypads must not exceed 1500 feet (457m)
when unshielded quad conductor
cable is used (750 feet if shielded cable is
used). This restriction is due to the capacitive effect on the data lines when
quad cable is used.
Transformer Wiring Table
Distance of Transformer Wire Gauge
From the Control Panel To Use
Up to 50 feet # 20
50–100 feet # 18
100–250 feet # 16